GEM (Government e-Marketplace) invites bids for an Automatic Contact Resistance Meter – 200A designed for auto offline measurement in live switchyards up to 765 kV. Located in Central Delhi, Delhi, the procurement emphasizes portability, robust accessories, and a rugged carrying case. Key differentiators include inbuilt cooling, PC communication, data export, and a minimum 1-year warranty post-commissioning. The instrument must operate on standard AC or DC power with adequate safety protections, suitable for EMI/EMC and environmental testing regimes. Precise measurement capabilities and repeatable results in live conditions are required.

Technical Specifications & Requirements

  • Measurement Range: 0.01 μΩ to 3 Ω with auto-ranging capability
  • Test Current: 200 A or higher (selectable 50 A, 100 A, 150 A, 200 A)
  • Resolution: 0.01 μΩ up to 199.9 μΩ; 0.1 μΩ above 199.9 μΩ; 1 μΩ above 2 mΩ; 10 μΩ above 20 mΩ
  • Accuracy: ±1% ± 1 Digit; Display: 4-1/2 digit LCD with backlight
  • Operating Environment: 0°C to 55°C; Max Humidity 95% non-condensing; IP/safety compliance as per environment tests
  • Power & Connectivity: 90-275V AC 45-65Hz or 100-300V DC; onboard display plus PC interface for data export
  • Physical & Accessories: Inbuilt cooling, rugged carrying case, test leads and all essential accessories; compatible with EMI/EMC and safety/IP environmental tests
  • Software & Data: Ability to test, store, export data; Windows PC communication; standalone kit with onboard controls
  • Warranty: Minimum 1 year from commissioning; comprehensive coverage including cables and accessories

Terms, Conditions & Eligibility

  • Warranty/Guarantee: Minimum 1 year from date of commissioning at the specified station
  • Live Switchyard Capability: Suitable for automatic offline measurement in live switchyards up to 765 kV; repeatability and EMI immunity required
  • Power & Cooling: Inbuilt cooling; compatible with single-phase supply (90-275V AC) or DC (100-300V)
  • Documentation & Compliance: EMI/EMC, safety, IP/environment test compatibility; complete set of test leads and rugged carrying case included
  • Delivery/Installation: Not specified in detail; bidder to confirm commissioning at client station and practical deployment in central Delhi facilities

Key Specifications

  • Measurement Range: 0.01 μΩ to 3 Ω, Auto ranging

  • Test Current: 200 A or Higher (50A, 100A, 150A, 200A selectable)

  • Resolution: 0.01 μΩ up to 199.9 μΩ; 0.1 μΩ above 199.9 μΩ; 1 μΩ above 2 mΩ; 10 μΩ above 20 mΩ

  • Accuracy: ±1% ± 1 Digit

  • Operating Temperature: 0°C to 55°C; Relative Humidity: 95% non-condensing

Terms & Conditions

  • EMD amount unspecified in data; bidders must verify

  • Minimum 1-year warranty from commissioning at client site

  • Suitable for live switchyard measurements up to 765 kV with EMI/EMC and safety compliance

Important Clauses

Payment Terms

Not specified in provided data; confirm with procurement

Delivery Schedule

Commissioning at client station post-delivery; exact timeline to be confirmed

Penalties/Liquidated Damages

Not specified in data; verify terms during bid submission

Bidder Eligibility

  • Experience in supplying contact resistance meters for high-voltage switchyards

  • Demonstrated capability for EMI/EMC and safety testing compliance

  • Financial stability evidenced by audited statements

Technical Specifications 1 Item

Item #1 Details

View Catalog
Category Specification Requirement
Construction Inbuilt printer provided Yes
Generic No. of Line display on LCD 4 Or higher
Generic Warranty 1, 2 Or higher
Generic Relative Humidity =<95% RH
Generic Display digits of LCD 4-1/2
Generic Maximum Operating Temperature 55.0
Generic Accessories Output lead Set, Mains Cord, Mains Protection fuse 5A, User Manual, Calibration Certificate, Carrying Case, Software CD, USB Cord, Battery Charger, Spare Fuses, C Clamp
Generic Display Type LCD
Generic Memory(No. of test result storage) 1000
Performance Parameter Test Current configurable, Ampere 200 Or higher
Performance Parameter Minimum measurement Accuracy +/- 1%
Performance Parameter Minimum resolution 0.1, 1, 10 Or higher
Performance Parameter Maximum resistance measuring Range 3000 Or higher
Power Supply Power supply function Both
Power Supply Inbuilt Battery type Li-Ion

AI-Powered Bidder Prediction

Companies most likely to bid

Unlock Bidder Insights

AI predictions on likely bidders

Required Documents

1

GST Registration Certificate

2

Permanent Account Number (PAN) Card

3

Experience certificates for similar resistance meter deployments

4

Financial statements showing solvency/creditworthiness

5

EMD/Security deposit documentation

6

Technical bid documents demonstrating compliance with listed specifications

7

OEM authorization or authorised distributor certificate

8

Product data sheets and compliance certificates

9

Warranty terms and service/support commitments

Frequently Asked Questions

How to bid for the contact resistance meter tender in Delhi 2025

Bidders should submit GST, PAN, experience proofs, financial statements, EMD, OEM authorisation, and technical compliance documents. The tender demands a 200A test current, 0.01 μΩ resolution, and 765 kV live-switchyard suitability. Ensure data export capability and inbuilt cooling are met. Confirm warranty and commissioning requirements with GEM.

What documents are required for the resistance meter procurement in Central Delhi

Required submissions include GST certificate, PAN card, company financials, past project experience certificates, EMD documentation, OEM authorisation, product datasheets, and warranty/AMC commitments. Technical bid must demonstrate 0.01 μΩ minimum resolution and 200A test current per ATC.

What are the technical specifications for the 200A resistance meter in this bid

The meter must measure 0.01 μΩ to 3 Ω with auto-ranging, provide 200 A selectable current (50/100/150/200 A), offer 0.01 μΩ resolution up to 199.9 μΩ, 0.1 μΩ above, and 1 μΩ above 2 mΩ, with ±1% ±1 Digit accuracy and a 4-1/2 digit LCD display.

What is the required warranty and commissioning terms for this tender

The supplier must provide a minimum 1-year warranty from the date of successful commissioning at the client station. All accessories, cables, and the rugged carrying case should be included, with coverage extending to performance under EMI/EMC and safety tests.

What are the environmental and safety requirements for the device

The device must operate 0°C to 55°C with 95% RH non-condensing, pass EMI/EMC, safety, and IP/environmental tests, and include inbuilt cooling. It should be suitable for live switchyard use up to 765 kV, with protective features against short circuit and transient surges.

What equipment accessories are expected with the meter delivery

Delivery must include all required test leads, probes, connectors, a rugged carrying case, calibration certificates, software for data storage/export, and a Windows-compatible interface for PC communication.

How will data be stored and exported from the resistance meter

The kit must store test results and export to a Windows-based computer; ensure software supports data logging, test result export in standard formats, and seamless PC-side analysis for commissioning reports.

What is the power supply specification for field operation

The meter supports 90-275V AC at 45-65Hz or 100-300V DC input. It must function with a standard single-phase supply and provide stable operation during field testing in live switchyards.