Kamdhenu University invites bids for Power Generator - DG Set (up to 900 KVA) (Q2) in BANASKANTHA, GUJARAT. Quantity: 1. Submission Deadline: 12-11-2025 15: 00: 00. Submit your proposal before the deadline.
Open Tender for Power Generator - DG Set (up to 900 KVA) in BANASKANTHA, GUJARAT
Posted
28 Oct 2025, 02:25 pm
Deadline
12 Nov 2025, 03:00 pm
EMD
₹45,000
Value
₹15,00,000
Location
Progress
Quantity
1
Bid Type
Two Packet Bid
Categories
1
Technical Specifications
1 Item
Item #1 Details
View Catalog| Category | Specification | Requirement |
|---|---|---|
| Power Generator INSTALLATION CONFIGURATIONS | Power Generator installation configurations as defined in CPWD General Specifications for Electrical works - Part VII (DG Set) | Fixed (Power Generators are permanently installed)", Transportable (Skid Mounted) (Power Generators are not permanently installed)", Mobile (Trailer mounted) (Power Generators having an integral chassis fitted with wheels) " |
| OUTPUT CAPACITY RATING/ PHASE | Nominal Rated Capacity (kVA) | 100 |
| ENGINE | Rated Engine Power (kWm) | 110 % of the required powered at STP(Standard Temperature Pressure) i.e equal to (Nominal Rated Capacity (KVA) of power generator Any Auxilary power Consumption by the Power generator) x Power factor(0.8) / Alternator efficience Or higher |
| ENGINE | Type of Engine cooling | Liquid Cooled |
| ENGINE | Type of governer | Electronic Or higher |
| ENGINE | Number of cylinders (nos) | 6 |
| ENGINE | Rated RPM of Engine (RPM) | 1500 |
| ENGINE | Fuel | High Speed Diesel (HSD) |
| ENGINE | Starting voltage (volt) | 12 |
| ENGINE | Salient Features of Engine | No derating applicable upto 4500 above MSL of altitude at 25 degree celcius, Turbo Charged Engine |
| GOVERNING CLASS | "Maximum Change of Speed as a Percentage of Rated Speed on suddenly taking-off the rated load(Transient) " | 15 |
| GOVERNING CLASS | "Maximum Recovery Time in Seconds on suddenly taking-off the rated load(Transient) " | 15.0 |
| GOVERNING CLASS | Maximum Change of Speed as a Percentage of Rated Speed on suddenly taking-off the rated load(Permanent) | 5 |
| GOVERNING CLASS | "Maximum Change of Speed as a Percentage of Rated Speed On a change of load, both on and off, by all steps of 25 percent of the rated load (Transient) " | 4 |
| GOVERNING CLASS | "Maximum Recovery Time in Seconds on a change of load, both on and off, by all steps of 25 percent of the rated load(Transient) " | 5.0 |
| GOVERNING CLASS | "Maximum Change of Speed as a Percentage of Rated Speed On a change of load, both on and off, by all steps of 25 percent of the rated load (Permanent) | 1.5 |
| ALTERNATOR | Alternator Voltage Rating | 415.0 |
| ALTERNATOR | Efficiency at rated Power factor at 75% of full Load | 90.0 - 100.0 Or higher |
| ALTERNATOR | Conformity to Indian Standard (for Alternator) | Generally conforming to IS:13364 (Part-2) latest (Above 20 KVA) |
| ALTERNATOR | Voltage Regulation Grade | VG 3 Or higher |
| CONTROL PANEL | Control Panel | AMF Control Panel |
| CONTROL PANEL | Control Panel Location | Outside the Canopy |
| CONTROL PANEL | IP Rating of Control Panel | IP 53, IP 54, IP 55 Or higher |
| CONTROL PANEL | Display meters in the control panel (with appropriate rating and accuracy class ) - inclusive in the scope of supply | Voltmeter, Ammeter, Frequency meter, Power Factor meter, Multifunctional Digital display meter (displaying Voltage, Current, Frequency, Power Factor) |
| BATTERY | Battery Type & Specification | "Low Maintenance free to IS: 14257 for high cranking performance" |
| BATTERY | No of batteries | 1 |
| SALIENT FEATURES | Salient Features of Power Generator | Glass window on Accoustic Enclosure in front of the Control Panel, Emergency Stop outside the Accoustic Enclosure |
| TRAILER | Trailer | NA for Fixed/Skid Mounted Power Generator |
| TRAILER | Pay load of the Trailer | 0, 500, 1000, 2000 Or higher |
| SCOPE OF INSTALLATION | Installation | with installation - inclusive in the scope of supply Or higher |
| WARRANTY/SERVICES | Warranty on Complete power genertor/DG Set | 36 Or higher |
| WARRANTY/SERVICES | Number of preventive maintenance visits offered in an year during warranty period (Supply of all consumables is the buyer's responsibilty)* | 1, 2, 3 |
| TEST REPORTS | Test report Available for (Test/approval) | Type Approval Certificate for the specified rating of the Power Generator from any of the designated agency authorized by CPCB, COP Certificate for engine, Type test report and Endurance test report for Engine as per IS: 10001 latest / IS: 10002 latest, Type test report for Alternator as per IS:13364 (Part-1) latest / IS:13364 (Part-2) latest to prove conformity to the specifications |
AI-Powered Bidder Prediction
Companies most likely to bid
Unlock Bidder Insights
AI predictions on likely bidders
Required Documents
Experience Criteria
Past Performance
Bidder Turnover
Certificate (Requested in ATC)
OEM Authorization Certificate
OEM Annual Turnover *In case any bidder is seeking exemption from Experience / Turnover Criteria
the supporting documents to prove his eligibility for exemption must be uploaded for evaluation by the buyer
Similar Tenders
Power Generator - DG Set (up to 900 KVA)
Higher Education Department Odisha
CUTTACK, ODISHA
Power Generator - DG Set (up to 900 KVA)
Public Works Department Madhya Pradesh
UMARIA, MADHYA PRADESH
Download FREE!
Access all tender documents at no cost
Documents 4
GeM-Bidding-8520372.pdf
Main Document
CATALOG-Specification-1
CATALOG Specification