Compression Dead end for Lapwing ACSR Conductor,Grading Ring for Lapwing ACSR Conductor,Corona cont
Power Grid Corporation Of India Limited
Bid Publish Date
24-Nov-2025, 2:20 pm
Bid End Date
05-Dec-2025, 3:00 pm
Location
Progress
Quantity
247
Category
Material and labour in replacement for ACSR conductor
Bid Type
Two Packet Bid
Indian Army invites bids for Material and labour in replacement for ACSR conductor, Supply and erect steel tubular swaged poles comple, Supply and erect steel tubular swaged poles, Supply and fixing in replacement of stay assembly, Material and Labour in replacement cross arms bracings supports clamps, Material and labour for restrainging ACSR conductor 33KV HT line, Prunning of trees of over head 33KV HT lines, Supply and Fixing in replacement loop type porcelain, Replacement of pin type porcelain white brown or green insulator, Supply and fixing in replacement of lighting arrestor metal oxide type, Supply installation commissioning in replacement and testing in replacement, Excavation in trenches in soft oblique loose soil, Removal of surplus spoil to a distance, Material and labour PCC, Material and labour for PCC, Cable end termination jointing kit for 33 KV in JAMMU, JAMMU & KASHMIR. Quantity: 247. Submission Deadline: 05-12-2025 15: 00: 00. Submit your proposal before the deadline.
Power Grid Corporation Of India Limited
Indian Army
Indian Army
Indian Army
WEST DELHI, DELHI
Indian Army
VADODARA, GUJARAT
Tender Results
Loading results...
| Item # | Title | Description | Quantity | Unit | Consignee | Delivery (Days) |
|---|---|---|---|---|---|---|
| 1 | Material and labour in replacement for ACSR conductor | Material and labour in replacement for ACSR conductor any size drawn straight horizontal on over head lines on existing poles including binding with insulators weight of conductor shall be measured straight horizontal distance between centre of two adjacent HT oblique LT poles and calculating weight of conductor of size length by adding 3% extra for sag jointing jumpers etc | 9 | qtls | consignee@geafjmu | 45 |
| 2 | Supply and erect steel tubular swaged poles comple | Supply and erect steel tubular swaged poles complete with cast iron base plate final taper plug bolts nuts and screws as specified type 410 SP 55 11 mtr long erecting in position all. | 4 | each | consignee@geafjmu | 45 |
| 3 | Supply and erect steel tubular swaged poles | Supply and erect steel tubular swaged poles complete with cast iron base plate final taper plug bolts nuts and screws as specified type 410 SP 64 12 mtr long erecting in position all | 3 | each | consignee@geafjmu | 45 |
| 4 | Supply and fixing in replacement of stay assembly | Supply and fixing in replacement of stay assembly comprising of 7 oblique 2.50mm galvanized MS stay wire of reqd length fixed to poles with and including of FI clamps made out of FI 40x6mm and nuts bolts washers of suitable size MS stay bow 14mm dia galvanized 40cm long MS galvanised stay rod threaded with nut 16mm dia 21 Cm long with washers MS stay plate galvanized 230x30x6mm incl necessary Excavation and PCC all | 6 | each job | consignee@geafjmu | 45 |
| 5 | Material and Labour in replacement cross arms bracings supports clamps | Material and Labour in replacement cross arms bracings supports clamps and back plates fabricated from structural steel sections including nut bolts washers welding bending cold and hot drilling holes for bolts in any shape or size as indicate or directed and inclusive of one primer coat one under coat and one finishing coat of paint. | 2 | qtls | consignee@geafjmu | 45 |
| 6 | Material and labour for restrainging ACSR conductor 33KV HT line | Material and labour for restrainging ACSR conductor 33KV HT line providing suitable proper sag all as specified and directed. | 20 | each span | consignee@geafjmu | 45 |
| 7 | Prunning of trees of over head 33KV HT lines | Prunning of trees of over head 33KV HT lines by taking proper shutdown and removing the same from site upto a distance of 50 mtr all as directed by Engr in Charge. | 70 | each span | consignee@geafjmu | 45 |
| 8 | Supply and Fixing in replacement loop type porcelain | Supply and Fixing in replacement loop type porcelain white brown or green large size with cover dimensions of 90mmx140mm clearance of whole 25.5 mm as specified and directed by Engr in charge. | 40 | each | consignee@geafjmu | 45 |
| 9 | Replacement of pin type porcelain white brown or green insulator | Replacement of pin type porcelain white brown or green insulator including one galvanized mild steel spindle two galvanised iron washers and one galvanised nut 50mm height 65mm dia for working pressure 33000 volts grade all | 70 | each | consignee@geafjmu | 45 |
| 10 | Supply and fixing in replacement of lighting arrestor metal oxide type | Supply and fixing in replacement of lighting arrestor metal oxide type gap less heavy duty single pole suitable for rated system voltage 33 KV and working rated 65 Kilo Amp normal discharge. | 1 | set of three | consignee@geafjmu | 45 |
| 11 | Supply installation commissioning in replacement and testing in replacement | Supply installation commissioning in replacement and testing in replacement of switch Air break Gang operated with insulator switch Triple pole mechanicaly operated mounted on insulator and steel frame for current rating 200 Amp operating Voltage 33 KV out door vertical mounted type complete with locking arrengement assembly operating Rod of 25 mm dia bore medium grade GI pipe of suitable length worked out from ground level and handle complete with lock and two Nos keys incl flat iron clamp 50mm x 6mm MS channel of suitable size and length for fixing GOD including nut bolt washers including taking down existing unservicable set all | 1 | each | consignee@geafjmu | 45 |
| 12 | Excavation in trenches in soft oblique loose soil | Excavation in trenches in soft oblique loose soil not exceeding 1.50 m wide and not exceeding 1.50 m in depth for foundation of poles stay cable pipes etc and getting out complete all | 6 | cum | consignee@geafjmu | 45 |
| 13 | Removal of surplus spoil to a distance | Removal of surplus spoil to a distance not exc. 50m and depositing where directed at a level not exc. 1.5m above the starting point complete all as specified. | 6 | cum | consignee@geafjmu | 45 |
| 14 | Material and labour PCC | Material and labour for PCC 1 ratio 4 ratio 8 type D 2 using 40mm graded broken stone aggregate as in mass concrete | 6 | cum | consignee@geafjmu | 45 |
| 15 | Material and labour for PCC | Material and labour for PCC 1 ratio 3 ratio 6 type D 2 using 20mm graded broken stone aggregate as in mass concrete | 1 | cum | consignee@geafjmu | 45 |
| 16 | Cable end termination jointing kit for 33 KV | Cable end termination jointing kit for 33 KV Earthed grade cable outdoor type heat shrink type joint complete with jointing material and accessories suitable for single core XLPE Sqmm | 2 | each | consignee@geafjmu | 45 |