Distribution Transformer, 3 Phase, 11 kV > 200 KVA up to and Including 2500 KVA
South East Central Railway
BILASPUR, CHHATTISGARH
Bid Publish Date
25-Dec-2025, 8:57 pm
Bid End Date
15-Jan-2026, 9:00 pm
EMD
₹1,00,000
Location
Progress
Quantity
1
Bid Type
Two Packet Bid
West Bengal Transport Corporation Limited invites bids for the supply, installation, testing and commissioning of 3-phase distribution transformers 11 kV (HV) to 0.415 kV LV, 200 kVA up to 2500 kVA at Kolkata 700001. The tender requires EMD ₹1,00,000 and encompasses delivery, on-site installation, testing, commissioning and operator training. Technical emphasis lies on energy efficiency, BEE Star ratings, standard testing and conformity to IS 1180 (Part 1):2014, with optional fittings and sound-level considerations. Unique aspects include stage inspections, transformer tank construction and comprehensive testing reports. This procurement targets compliant OEMs with a proven service footprint in West Bengal and a robust after-sales network.
Transformer rating range from 200 kVA to 2500 kVA
HV nominal voltage: 11 kV; LV nominal voltage: 0.415 kV
Highest system voltage and no-load current specs to be as per IS 1180 and Annex-D
Tank material and minimum wall thickness for top, bottom and sides as per IS 1180
Painting requirements per Table 12 of IS 1180 (Pt.1):2014
Optional fittings: Buchholz relay, oil temp/winding temp indicators, lightning arrestors
EMD ₹1,00,000; bid validity and delivery terms aligned with buyer options
2-year OEM warranty with service center in West Bengal; mandatory certificates
Quantity flexibility up to ±25% with extended delivery period; installation included
Payment to be linked to delivery milestones; ensure GST compliance and documentary evidence
Delivery starts after order; option to extend duration with 30 days minimum if quantity scaled
LD terms not detailed; ensure adherence to delivery and performance benchmarks per contract
Proven track record in supply and installation of distribution transformers (200 kVA–2500 kVA)
Functional service center presence in West Bengal or ability to establish within 30 days
Compliance with IS 1180 (Pt.1):2014 and energy efficiency/BEE rating requirements
South East Central Railway
BILASPUR, CHHATTISGARH
E-municipalities - Eservices To Citizens And Employees Of Urban Local Bodies Of Uttar Pradesh
SIDDHARTHNAGAR, UTTAR PRADESH
E-municipalities - Eservices To Citizens And Employees Of Urban Local Bodies Of Uttar Pradesh
GORAKHPUR, UTTAR PRADESH
N/a
SATARA, MAHARASHTRA
Indian Army
MEERUT, UTTAR PRADESH
Tender Results
Loading results...
| Category | Specification | Requirement |
|---|---|---|
| STANDARDS | Energy efficiency level | 1 |
| STANDARDS | BEE Star Rating | 1 |
| STANDARDS | Installation, Testing and Demonstration | Yes . Including Civil work, Yes . Excluding Civil work, No |
| STANDARDS | Minimum warranty on receipt of stores (in Months) | 30 |
| STANDARDS | Minimum warranty from the date of installation (in Months) | 24 |
| RATINGS | Nominal system voltage, HV ( in kV) | 11 |
| RATINGS | Nominal system voltage, LV ( in V) | 415 |
| RATINGS | Standard ratings (in kVA) | 1000 |
| RATINGS | Minimum basic insulation level (in kVP) | 75 |
| RATINGS | No load voltage ratios (in Volts) | 11000/433-250 |
| RATINGS | Highest system voltage for equipment (in kV) | 12 |
| RATINGS | Rated lightning impulse withstand voltage (in kV Peak) (Refer IS:1180 (Part 1):2014 Annex-D) | 75 |
| CONSTRUCTION | Core mateial | CRGO (as per IS:3024 latest) |
| CONSTRUCTION | Conductor (Winding) material | Copper |
| CONSTRUCTION | Type of Mounting | Pole Mounted, Ground Mounted |
| CONSTRUCTION | Noise level at rated voltage and freqeuncy, Maximum (in dB) | 45 |
| TRANSFORMER TANK | Transformer tank cover construction | Non-sealed, Bolted |
| TRANSFORMER TANK | Tank configuration with | With radiator fins |
| TRANSFORMER TANK | Material of transformer tank | Mild Steel |
| TRANSFORMER TANK | Minimum thickness of top and bottom material of transformer tank (in mm) | 6 |
| TRANSFORMER TANK | Minimum thickness of side material of transformer tank (in mm) | 4 |
| TRANSFORMER TANK | Material of Bolts/Nuts/Wahers exposed to atmosphere | Stainless steel (for upto 12 mm size), Brass (for upto 12 mm size), Electro Galvanized (for above 12 mm size), Hot Dip Galvanized (for above 12 mm size) |
| TRANSFORMER TANK | Gaskets wherever used shall conform to | Type III (as per IS:11149) Type C (as per IS:4253 (Pt.2) |
| TRANSFORMER TANK | Provision of conservator | Yes , for Non sealed type with Plain tank construction |
| Painting | Type of painting on inside of tank (hint: Refer Table 12 of IS:1180 (Pt.1):2014) | Oil resistant paint |
| Painting | Type of painting on External surface of tank (hint: Refer Table 12 of IS:1180 (Pt.1):2014) | Epoxy (Primer), Polyurethane (finish coat) |
| TAP CHANGER | Winding tapped | HV |
| TAP CHANGER | No. of positions (in Nos.) | 7 |
| TAP CHANGER | Voltage variation | +5% to -10% in steps of 2.5% for variation of HV |
| TERMINAL ARRANGEMENT | Transformer fitted with bushings of appropriate voltage and curent ratings on HV side | Yes. 3 Nos. (Conforming to IS:2099) |
| TERMINAL ARRANGEMENT | Transformer fitted with bushings of appropriate voltage and curent ratings on LV side | Yes. 4 Nos. (Conforming to IS:7421) |
| TERMINAL ARRANGEMENT | Suitable provision for adoption of cables of suitable size on LV side | Yes. For PVC/XLPE Cables |
| TERMINAL ARRANGEMENT | Cable End Box on HV side | Yes, No |
| TERMINAL ARRANGEMENT | Cable End Box on LV side | Yes |
| MARKING | Material of rating plate | Anodized aluminium |
| MARKING | Marking method on rating plate | Etching |
| MARKING | Rating and terminal marking plates combined into one plate | Yes |
| OPTIONAL FITTINGS | Suitable rating lightning arrestors | HT Side, 1 No. per phase |
| OPTIONAL FITTINGS | Bird guard | No |
| OPTIONAL FITTINGS | Terminal connectors | Yes |
| OPTIONAL FITTINGS | Oil temperature indicator and widning temperature indicator | Yes |
| OPTIONAL FITTINGS | Jacking pads | No |
| OPTIONAL FITTINGS | Buchholz relay | NoMagnetic oil level gauge with low oil level alarm contact |
| OPTIONAL FITTINGS | Magnetic oil level gauge with low oil level alarm contact | Yes for transformer above 1600 |
| OPTIONAL FITTINGS | Non return valve | Yes |
| OPTIONAL FITTINGS | Protection relay for sealed type transformers for internal parameters that is pressure, temperature, oil level and gas detection | No |
| OPTIONAL FITTINGS | Unidirectional flat rollers | Yes |
| OPTIONAL FITTINGS | Drain cum sampling valve | Yes with steel plug (for transformers upto 500 KVA) |
| OPTIONAL FITTINGS | Self protection / disconnection devices | On secondary side (as per IS/IEC:60947-2:2003, No |
| OPTIONAL FITTINGS | Expulsion fuse as disconnection device | On Primay side (as per IS:9385 (Part 2):1980, No |
| SERVICE CONDITION | Maximum altitude | <5000 m |
| TEST REPORTS & CERTIFICATIONS | Availability of type test reports to prove the confirmity of the specification from | NABL Accrediated |
| TEST REPORTS & CERTIFICATIONS | Agreed for stage Inspection as required by buyer | Yes |
| SPECIAL TEST REPORTS | Availability of test report for Determination of sound level test | No |
| SPECIAL TEST REPORTS | Availability of test report for short circuit withstand test | Yes |
| SPECIAL TEST REPORTS | Availability of test report for No load current at 112.5 % Voltage | Yes |
| SPECIAL TEST REPORTS | Availability of test report for Paint adhesion test | No |
| SPECIAL TEST REPORTS | BDV and moisture content of oil in the transformer | Yes for 1 No. |
| SPECIAL TEST REPORTS | Other requirements | Losses and Impedance values as per Cl.7.8 and Table 6 of IS:1180 (Part 1):2014 latest, Limits of temeprature-rise as per Cl.7.10 of IS:1180 (Part 1):2014 latest |
Discover companies most likely to bid on this tender
GST registration certificate
Permanent Account Number (PAN) card
Experience certificates for similar transformer supply/installations
Financial statements or turnover proof for last 3 years
EMD payment receipt or bank guarantee document
Technical bid documents showing conformity to IS 1180 (Part 1):2014
OEM authorization letter (if bidder is not the OEM)
Type test reports and compliance certificates for energy efficiency and BEE rating
Warranty certificates and service center details in West Bengal
Key insights about WEST BENGAL tender market
Bidders must submit GST, PAN, experience certificates, financials, EMD ₹1,00,000, OEM authorization if required, and type test reports demonstrating IS 1180 (Pt.1):2014 compliance, plus stage inspection readiness and BEE rating data.
Required documents include GST certificate, PAN, experience certificates for similar work, financial statements, EMD proof, OEM authorization, type test reports, warranty certificates, and service center details in West Bengal.
Specifications cover HV 11 kV, LV 0.415 kV, standard megavolt-ampere rating range 200–2500 kVA, insulation levels, no-load current at 112.5% voltage, and compliance with IS 1180 (Pt.1):2014 Annex-D sound tests.
An OEM warranty of 2 years from final acceptance or installation completion is required, with supplier providing warranty certificates at delivery and establishing local service support in West Bengal.
Delivery scope includes supply, installation, testing and commissioning, plus operator training; delivery can be adjusted by ±25% quantity with minimum 30 extra days; stage inspections and testing reports are mandatory.
Bidder must have a dedicated service center in/state or establish one within 30 days of award; provide toll-free service support and an escalation matrix for service issues.
Transformers must meet energy efficiency levels, BEE Star Rating, IS 1180 (Pt.1):2014 standards, and provide BDV/oil moisture data plus paint adhesion and short-circuit test reports.
EMD is ₹1,00,000; payment terms align to delivery milestones and compliance with GST requirements, with documentation proving delivery and performance milestones for release.