Distribution Transformer, 3 Phase, upto and Including 200 KVA ISI Marked To IS 1180 (Part 1)
N/a
JAMMU, JAMMU & KASHMIR
Bid Publish Date
22-Jun-2026, 1:29 pm
Bid End Date
02-Jul-2026, 2:00 pm
Location
Progress
Quantity
1
Bid Type
Two Packet Bid
N/a announces a tender for Distribution Transformer, 3 Phase, upto and Including 200 KVA ISI Marked To IS 1180 (Part 1) (Q2) in JAMMU, JAMMU & KASHMIR. Quantity: 1. Submission Deadline: 02-07-2026 14: 00: 00. Last date to apply is approaching fast!
Tender Category
Goods
Bid To RA
No
Bid To RA Enabled
No
Item Category
Distribution Transformer, 3 Phase, upto and Including 200 KVA ISI Marked To IS 1180 (Part 1) (Q2)
End-to-end support — bid preparation, GeM registration, document filing & compliance by industry experts.
Free consultation · 24h response
Main Document
CATALOG Specification
GEM_GENERAL_TERMS_AND_CONDITIONS
N/a
JAMMU, JAMMU & KASHMIR
N/a
JAMMU, JAMMU & KASHMIR
N/a
RAJGARH, MADHYA PRADESH
Eastern Railway
MALDA, WEST BENGAL
Eastern Railway
MALDA, WEST BENGAL
Tender Results
Loading results...
| Category | Specification | Requirement |
|---|---|---|
| STANDARDS | Energy Efficiency Level | 2 |
| STANDARDS | BEE Star Rating | 2, 3, 4, 5 Or higher |
| RATINGS | Nominal System Voltage, HV ( in kV) | 11 |
| RATINGS | Nominal System Voltage, LV ( in Volt) | 433 |
| RATINGS | Standard Ratings (in kVA) | 63 |
| RATINGS | Minimum Basic Insulation Level (in kVp) | 75 |
| RATINGS | No Load Voltage Ratios (in Volts) | 11000/433-250 |
| RATINGS | Highest System Voltage for Equipment (in kV) | 12 |
| RATINGS | Rated Lightning Impulse withstand Voltage (in kV Peak) | 75 |
| CONSTRUCTION | Core Material | CRGO (as per IS:3024 latest) |
| CONSTRUCTION | Conductor (Winding) Material | Aluminium |
| CONSTRUCTION | Type of Mounting | Pole Mounted |
| CONSTRUCTION | Method of System Earthing | solidly earthed |
| CONSTRUCTION | Noise Level at Rated Voltage and Freqeuncy, Maximum (in dB) | 55 |
| TRANSFORMER TANK | Transformer Tank Cover Construction | Non-sealed, Bolted |
| TRANSFORMER TANK | Tank Configuration | With radiator fins |
| TRANSFORMER TANK | Minimum Thickness of Top and Bottom Material of Transformer Tank (in mm) | 5 |
| TRANSFORMER TANK | Minimum Thickness of Side Material of Transformer Tank (in mm) | 3.15 |
| TRANSFORMER TANK | Material of Bolts/Nuts/Washers | Hot Dip Galvanized (for above 12 mm size) |
| TRANSFORMER TANK | Provision of Conservator | Yes , for Non sealed type with Plain tank construction |
| PAINTING | Type of Painting on Inside of Tank | Hot oil resistant paint |
| PAINTING | Type of Painting on External Surface of Tank | Polyurethane (finish coat) |
| TAP CHANGER | Tap Changing Arrangement | Not applicable |
| TAP CHANGER | Winding Tapped | Not applicable |
| TAP CHANGER | Number of Positions | 0 |
| TAP CHANGER | Voltage Variation | Not applicable |
| TERMINAL ARRANGEMENT | Transformer Fitted with Bushings of Appropriate Voltage and Current Ratings on LV Side | Yes. 4 Nos. (Conforming to IS:7421) |
| TERMINAL ARRANGEMENT | Provision for Adoption of Cables of Suitable Size on LV Side | No |
| TERMINAL ARRANGEMENT | Cable End Box on HV side | No |
| TERMINAL ARRANGEMENT | Cable End Box on LV side | No |
| AIR CLEARANCE | Minimum Air Clearances in Cable Box | Without cable box |
| AIR CLEARANCE | Provision of Suitable Clamp-Type Bimetallic Connectors on HV and LV Terminals | Yes. For Bare bushing termination |
| MARKING | Material of Rating Plate | Anodized aluminium |
| MARKING | Marking Method on Rating Plate | Engraved |
| MARKING | Combined Rating and Terminal Marking Plate | Yes |
| OPTIONAL FITTINGS | Provision of Dehydrating Breather in lieu of Plain Breathing Device for Transformer | Yes |
| OPTIONAL FITTINGS | Provision of Filter Valve for Transformers | No |
| OPTIONAL FITTINGS | Provision of Bird Guard | No |
| OPTIONAL FITTINGS | Provision of Terminal Connectors | No |
| OPTIONAL FITTINGS | Provision of Pressure Relief Device or Explosion Vent (upto 200 KVA doe non-sealed type transformer) | No |
| OPTIONAL FITTINGS | Provision of Protection Relay for Sealed-Type Transformers for Monitoring Internal Parameters (Pressure, Temperature, Oil Level, and Gas Detection) | No |
| OPTIONAL FITTINGS | Provision of Anti-theft Stainless Steel Fasteners with Breakway Nut at top Cover | No |
| OPTIONAL FITTINGS | Provision of Drain Cum Sampling Valve | Yes with steel plug |
| OPTIONAL FITTINGS | Provision of Self Protection/Disconnection Devices | No |
| OPTIONAL FITTINGS | Provision of Expulsion Fuse as Disconnection Device | No |
| SPECIAL TEST REPORTS | Availability of Test Report for Determination of Sound Level Test | No |
| SPECIAL TEST REPORTS | Availability of Test Report for No Load Current at 112.5% Voltage | Yes |
| SPECIAL TEST REPORTS | Availability of Test Report for Paint Adhesion Test | No |
| SPECIAL TEST REPORTS | BDV and Moisture Content of Oil in the Transformer | Yes for 1 No. |
| SPECIAL TEST REPORTS | Other Requirements | Losses and Impedance values as per Cl.6.8 and Table 3 of IS:1180 (Part 1):2014 latest, Pressure test as per IS:1180 |
Discover companies most likely to bid on this tender
Past Performance
Bidder Turnover
Certificate (Requested in ATC)
OEM Authorization Certificate
OEM Annual Turnover
Additional Doc 1 (Requested in ATC) *In case any bidder is seeking exemption from Experience / Turnover Criteria
the supporting documents to prove his eligibility for exemption must be uploaded for evaluation by the buyer
Assam Electricity Grid Corporation Ltd
📍 KAMRUP, ASSAM
Madhya Pradesh Paschim Kshetra Vidyut Vitran Company Ltd
📍 INDORE, MADHYA PRADESH
Gujarat State Electricity Corporation Limited (gsecl) Vadodara
📍 ANAND, GUJARAT
Directorate Of Purchase And Stores
Brahmaputra Valley Fertilizer Corporation Limited (bvfcl)
📍 DIBRUGARH, ASSAM
Sign up now to access all documents
Main Document
CATALOG Specification
GEM_GENERAL_TERMS_AND_CONDITIONS