A tender has been published for Airports Authority Of India SITC of fire dampers, SITC of fire dampers in supply air duct Actuator torque 9Nm 230V. , SITC of fire dampers in supply air duct Actuator torque 20Nm, 230V. , Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular ducting 0. 8 mm thick, Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular ducting 1. 00 mm thick, Supply and fixing of acoustic lining, Supplying and fixing Nitrile rubber Insulation 19 mm, Dismantling of old Airconditioning Ducts, SITC of control panel for 230V Actuator. , SITC of AHU Tripping Panel, Supply of 2x1. 5 sqmm Copper Control Cables, Laying and fixing cable tray, Laying and fixing of XLPE power cable of 1. 1 KV on wall surface Upto 35 sq. mm, Supplying and making end termination, Integration of all devices for activiation of AHU in COIMBATORE, TAMIL NADU. Quantity: 4323 by. Submission Deadline: 24-08-2026 17: 00: 00. Check eligibility and apply.
Quantity
4323
Category
SITC of fire dampers
Bid Type
Two Packet Bid
Bid Validity
30 (Days)
Bid Type
Service
Evaluation
Total value wise evaluation
Inspection Required
No
Tech Clarification Time
3 Days
EMD Required
Yes
MII Purchase Preference
Yes
MII Preference Band
L1+20%
MSE Purchase Preference
Yes
MSE Preference Band
L1+15%
MSE Exemption/Relaxation
No
Startup Exemption/Relaxation
No
Bid Splitting Applied
No
Min. Avg. Annual Turnover
7
OEM Avg. Turnover
7
Past Performance
80 %
Experience Required
3 Year (s)
Arbitration Clause
No
Mediation Clause
No
Tender Category
Goods
Bid To RA
No
Bid To RA Enabled
No
Item Category
SITC of fire dampers , SITC of fire dampers in supply air duct Actuator torque 9Nm 230V. , SITC of fire dampers in supply air duct Actuator torque 20Nm, 230V. , Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular ducting 0.8 mm thick , Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular ducting 1.00 mm thick , Supply and fixing of acoustic lining , Supplying and fixing Nitrile rubber Insulation 19 mm , Dismantling of old Airconditioning Ducts , SITC of control panel for 230V Actuator. , SITC of AHU Tripping Panel , Supply of 2x1.5 sqmm Copper Control Cables , Laying and fixing cable tray , Laying and fixing of XLPE power cable of 1.1 KV on wall surface Upto 35 sq. mm , Supplying and making end termination , Integration of all devices for activiation of AHU
Advisory Bank
State Bank of India
Payment Timelines
Payments shall be made to the Seller within 30 days of issue of consignee receipt-cum-acceptance certificate (CRAC) and on-line submission of bills (This is in supersession of 10 days time as provided in clause 12 of GeM GTC)
Max Delivery Days
90
Delivery Locations
1
Delivery Cities
Coimbatore
Delivery Pincodes
641014
| Consignee | Address | City | State | Pincode | Quantity | Delivery Days | Additional Requirement |
|---|---|---|---|---|---|---|---|
| Senthilkumar S V | 641014,33AAACA6412D1ZF, Airports Authority Of India, Coimbatore International Airport, Coimbatore | Coimbatore | Tamil Nadu | 641014 | 12 | 90 | - |
End-to-end support — bid preparation, GeM registration, document filing & compliance by industry experts.
Free consultation · 24h response
Main Document
OTHER
BOQ
BOQ
OTHER
GEM_GENERAL_TERMS_AND_CONDITIONS
SITC of fire dampers
Supplying, Fixing,testing and commissioning of fire dampers in supply air duct or main branch and return air path as and where required of required sizes including control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. Fire Damper
SITC of fire dampers in supply air duct Actuator torque 9Nm 230V.
Supplying, Fixing,testing and commissioning of fire dampers in supply air duct or main branch and return air path as and where required of required sizes including control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. Actuator torque 9Nm, 230V.
SITC of fire dampers in supply air duct Actuator torque 20Nm, 230V.
Supplying, Fixing,testing and commissioning of fire dampers in supply air duct or main branch and return air path as and where required of required sizes including control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. Actuator torque 20Nm, 230V.
Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular ducting 0.8 mm thick
Supply installation balancing and commissioning of fabricated at site GSS sheet metal rectangular or round ducting complete with neoprene rubber gaskets elbows splitter dampers vanes hangers supports etc. as per approved drawings and specifications of following sheet thickness complete as required. Site fabricated GSS sheet metal rectangular ducting as per IS 655 2006 0.8 mm thick
Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular ducting 1.00 mm thick
Supply installation balancing and commissioning of fabricated at site GSS sheet metal rectangular or round ducting complete with neoprene rubber gaskets elbows splitter dampers vanes hangers supports etc. as per approved drawings and specifications of following sheet thickness complete as required. Site fabricated GSS sheet metal rectangular ducting as per IS 655 2006 1.00 mm thick
Supply and fixing of acoustic lining
Supply and fixing of acoustic lining of supply air duct and plenum with 25 mm thick resin bonded glass wool having density of 32 kg or meter cube with 25 mm X 25 mm GI section of 1.25 mm thick at 600 mm centre to centre covered with Reinforced Plastic tissue paper and 0.5 mm thick perforated aluminum sheet fixed to inside surface of ducts with cadmium plated nuts bolts stick pins CPRX compound etc. complete as required and as per specifications.
Supplying and fixing Nitrile rubber Insulation 19 mm
Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber Class O insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required. Nitrile rubber Insulation 19 mm
Dismantling of old Airconditioning Ducts
Dismantling of old Airconditioning Ducts from the AC system including removal of insulations supports etc. complete to make Provision for connection of Fire Damper and shifting the same to dismantled stores of AAI.
SITC of control panel for 230V Actuator.
Supply Instalation Testing and Commissioning of control panel for 230V Actuator.
SITC of AHU Tripping Panel
Supply Installation Testing and Commissiong of AHU Tripping Panel in Sheet Steel enclosure consists of intelligent addressable input or output loop powered relay module volt free contacts suitable for functioning via fire alarm loop.
Supply of 2x1.5 sqmm Copper Control Cables
Supply of 2 x 1.5 sqmm Copper Control Cables XLPE Insulated PVC Innersheathed Armoured Extruded PVC Type ST2 Sheathed 650 V or 1100 V Grade as per IS 7098 Part 1 1988.
Laying and fixing cable tray
Laying and fixing of one number PVC insulated and PVC sheathed or XLPE power cable of 1.1 KV grade of following size on cable tray as required. upto 35 Sq.mm.
Laying and fixing of XLPE power cable of 1.1 KV on wall surface Upto 35 sq. mm
Laying and fixing of one PVC insulated and PVC sheathed or XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm clamped with 1mm thick saddle.
Supplying and making end termination
Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated and PVC sheathed or XLPE copper conductor cable 1.1 KV grade as required.
Integration of all devices for activiation of AHU
Integration of all devices for activiation of AHU tripping in the event of fire detection interfacing with the existing fire dedection system including installation or modification or upgradation of program of all fire alarm panels in the system Testing and commissioning of the system complete as required and as per the direction of the enginner in charge. The scope of work also includes dismantling of unwanted BMS devices from the system wherever required.
| Item # | Title | Description | Quantity | Unit | Consignee | Delivery (Days) | Price Trends |
|---|---|---|---|---|---|---|---|
| 1 | SITC of fire dampers | Supplying, Fixing,testing and commissioning of fire dampers in supply air duct or main branch and return air path as and where required of required sizes including control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. Fire Damper | 12 | sq mm | svsenthilkumar | 90 | |
| 2 | SITC of fire dampers in supply air duct Actuator torque 9Nm 230V. | Supplying, Fixing,testing and commissioning of fire dampers in supply air duct or main branch and return air path as and where required of required sizes including control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. Actuator torque 9Nm, 230V. | 8 | each | svsenthilkumar | 90 | |
| 3 | SITC of fire dampers in supply air duct Actuator torque 20Nm, 230V. | Supplying, Fixing,testing and commissioning of fire dampers in supply air duct or main branch and return air path as and where required of required sizes including control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. Actuator torque 20Nm, 230V. | 12 | each | svsenthilkumar | 90 | |
| 4 | Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular ducting 0.8 mm thick | Supply installation balancing and commissioning of fabricated at site GSS sheet metal rectangular or round ducting complete with neoprene rubber gaskets elbows splitter dampers vanes hangers supports etc. as per approved drawings and specifications of following sheet thickness complete as required. Site fabricated GSS sheet metal rectangular ducting as per IS 655 2006 0.8 mm thick | 20 | sq mm | svsenthilkumar | 90 | |
| 5 | Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular ducting 1.00 mm thick | Supply installation balancing and commissioning of fabricated at site GSS sheet metal rectangular or round ducting complete with neoprene rubber gaskets elbows splitter dampers vanes hangers supports etc. as per approved drawings and specifications of following sheet thickness complete as required. Site fabricated GSS sheet metal rectangular ducting as per IS 655 2006 1.00 mm thick | 50 | sq mm | svsenthilkumar | 90 | |
| 6 | Supply and fixing of acoustic lining | Supply and fixing of acoustic lining of supply air duct and plenum with 25 mm thick resin bonded glass wool having density of 32 kg or meter cube with 25 mm X 25 mm GI section of 1.25 mm thick at 600 mm centre to centre covered with Reinforced Plastic tissue paper and 0.5 mm thick perforated aluminum sheet fixed to inside surface of ducts with cadmium plated nuts bolts stick pins CPRX compound etc. complete as required and as per specifications. | 50 | sq mm | svsenthilkumar | 90 | |
| 7 | Supplying and fixing Nitrile rubber Insulation 19 mm | Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber Class O insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required. Nitrile rubber Insulation 19 mm | 20 | sq mm | svsenthilkumar | 90 | |
| 8 | Dismantling of old Airconditioning Ducts | Dismantling of old Airconditioning Ducts from the AC system including removal of insulations supports etc. complete to make Provision for connection of Fire Damper and shifting the same to dismantled stores of AAI. | 60 | sq mm | svsenthilkumar | 90 | |
| 9 | SITC of control panel for 230V Actuator. | Supply Instalation Testing and Commissioning of control panel for 230V Actuator. | 10 | each | svsenthilkumar | 90 | |
| 10 | SITC of AHU Tripping Panel | Supply Installation Testing and Commissiong of AHU Tripping Panel in Sheet Steel enclosure consists of intelligent addressable input or output loop powered relay module volt free contacts suitable for functioning via fire alarm loop. | 20 | each | svsenthilkumar | 90 | |
| 11 | Supply of 2x1.5 sqmm Copper Control Cables | Supply of 2 x 1.5 sqmm Copper Control Cables XLPE Insulated PVC Innersheathed Armoured Extruded PVC Type ST2 Sheathed 650 V or 1100 V Grade as per IS 7098 Part 1 1988. | 2,000 | meter | svsenthilkumar | 90 | |
| 12 | Laying and fixing cable tray | Laying and fixing of one number PVC insulated and PVC sheathed or XLPE power cable of 1.1 KV grade of following size on cable tray as required. upto 35 Sq.mm. | 1,500 | rmt | svsenthilkumar | 90 | |
| 13 | Laying and fixing of XLPE power cable of 1.1 KV on wall surface Upto 35 sq. mm | Laying and fixing of one PVC insulated and PVC sheathed or XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm clamped with 1mm thick saddle. | 500 | rmt | svsenthilkumar | 90 | |
| 14 | Supplying and making end termination | Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated and PVC sheathed or XLPE copper conductor cable 1.1 KV grade as required. | 60 | each | svsenthilkumar | 90 | |
| 15 | Integration of all devices for activiation of AHU | Integration of all devices for activiation of AHU tripping in the event of fire detection interfacing with the existing fire dedection system including installation or modification or upgradation of program of all fire alarm panels in the system Testing and commissioning of the system complete as required and as per the direction of the enginner in charge. The scope of work also includes dismantling of unwanted BMS devices from the system wherever required. | 1 | job | svsenthilkumar | 90 |
Experience Criteria
Past Performance
Bidder Turnover
Certificate (Requested in ATC)
OEM Authorization Certificate
OEM Annual Turnover
Additional Doc 1 (Requested in ATC)
Additional Doc 2 (Requested in ATC)
Additional Doc 3 (Requested in ATC)
Additional Doc 4 (Requested in ATC)
Compliance of BoQ specification and supporting document *In case any bidder is seeking exemption from Experience / Turnover Criteria
the supporting documents to prove his eligibility for exemption must be uploaded for evaluation by the buyer