SITC of free standing, outdoor cubicle type microprocessor based AMF panel 30 KVA,Supplying, laying
Bharat Sanchar Nigam Limited Portal(bsnl)
ERNAKULAM, KERALA
Progress
Quantity
1548
Category
Attending emergency break down of HT services
Bid Type
Two Packet Bid
Bharat Sanchar Nigam Limited Portal(bsnl) has released a public tender for Attending emergency break down of HT services, Reconditioning of HT panel, Filtration of Transformer oil, Arresting of Transformer Oil leakage, Top up of transformer oil, Replacement of silica gel breather, General servicing of 3 panel HT panel, 230V AC 80 or 100 Wats Space Heaters, Heavy duty stem Type Safety Thermostat, 6 Amps DP MCB, Supply and wiring of 2. 5 sqmm copper wire, 2core x1. 5 sqmm Copper Armoured Cable, Monoplast sealings for all HT terminations, General servicing of ACB in the MV panel, General servicing of MV panel, Cleaning of HT Yard, General servicing of existing Air Break switch, 63 Amps 3P MCB for Capacitors, 63 Amps HRC Fuse Links, 6 Amps HRC Fuse Links, LED indication lamps, 20 KVAR Capacitor, 10 KVAR Capacitor, 5 KVAR Capacitor, 96 x 96 mm Digital Ammeter, 95 Sqmm XLPE HT Cable, Heat Shrinkable joint kit, Testing of the existing IDMT relay, Testing of earth pits, Supply and fixing of 11 KV grade post top or pin Insulator, Supplying and fixing of 9KV, 5KA rating Lightning arresters in HYDERABAD, TELANGANA. Quantity: 1548. Submission Deadline: 11-08-2025 17: 00: 00. Download documents and apply online.
Main Document
OTHER
BOQ
BOQ
ATC
GEM_GENERAL_TERMS_AND_CONDITIONS
Bharat Sanchar Nigam Limited Portal(bsnl)
ERNAKULAM, KERALA
Hindustan Petroleum Corporation Ltd
VIZIANAGARAM, ANDHRA PRADESH
Bharat Petroleum Corporation Ltd
SANGLI, MAHARASHTRA
Hindustan Petroleum Corporation Ltd
EAST GODAVARI, ANDHRA PRADESH
Hindustan Petroleum Corporation Ltd
Tender Results
Loading results...
| Item # | Title | Description | Quantity | Unit | Consignee | Delivery (Days) |
|---|---|---|---|---|---|---|
| 1 | Attending emergency break down of HT services | Attending emergency break down of HT services/MV Panels such as indoor/outdoor type Transformer substation, Transformer Interchange, ACB breakdowns, HT Kits, AB switches, correction of Low PF by checking Capacitor panel etc.,by identifying the fault, isolating/ rectifying/ bypass the fault, restoration of permanent/ temporary supply including Meggering and checking of 11kv Insulators, CT/PT, Transformers, HT cable and structure with 5000/2500 volts Insulation Tester, cleaning of HG fuse, arcing rods, providing new HG fuses etc., complete as reqd. | 10 | jobs | sdee_sgd_bsnl | 365 |
| 2 | Reconditioning of HT panel | Reconditioning of HT panel by Spray painting including cleaning of rust in busbar and cable chambers, cleaning of HT spouts with CTC, providing heating processor remove moisture, applying of 2 coats synthetic enamel paint in bus bar chamber, cable chamber and out side of total HT Panel, providing new hardware for all covers, closing of any extra holes in cable chambers as reqrd., | 2 | jobs | sdee_sgd_bsnl | 365 |
| 3 | Filtration of Transformer oil | Filtration of Transformer oil for 160/250/315 /400 KVA Indoor/Outdoor transformer at site till the dielectric strength of oil reaches to 40 KV and holds for 1 minute including such as removal of all suspended particles like dust, rust, scales, colloidal carbon oxidation sludge etc., Degassing and Dehumidification of transformer oil under vacuum. Circulation of heated oil and filling of treated oil in transformer tank. De-acidification by evaporation and absorption method and including transportation of filtering machine, providing test certificate etc., as required. | 39 | jobs | sdee_sgd_bsnl | 365 |
| 4 | Arresting of Transformer Oil leakage | Arresting of Transformer Oil leakage from LT side of 160/250 KVA Transformer including disconnection of HT Jumpers, removing of 2 nos LT cables, removing of top cover of Transformer, replacing of 6 mm thick gaskets and Oil seals at 16mm brass bushings, refixing the top cover and LT cables etc., as req. | 4 | jobs | sdee_sgd_bsnl | 365 |
| 5 | Top up of transformer oil | Top up of transformer oil in the conservator tank up to the minimum level after filtration of the transformer oil in Transformers, and HT Panels etc., as req. | 500 | ltrs | sdee_sgd_bsnl | 365 |
| 6 | Replacement of silica gel breather | Supplying and fixing of silica gel breather including removing the old breather etc., as required. | 32 | nos | sdee_sgd_bsnl | 365 |
| 7 | General servicing of 3 panel HT panel | General servicing of 3 panel HT panel consisting of 1No isolator and 2No of OCB of 400A capacity, checking of bus bar, checking of cable chamber, checking of 50Volts DC supply, checking of spring tension in the trip bridge, applying of grease, oil, cleaning of HT terminals male and female contacts, checking of oil level in OCB, checking of strip heaters and AC supply, submitting of test report as required | 8 | jobs | sdee_sgd_bsnl | 365 |
| 8 | 230V AC 80 or 100 Wats Space Heaters | Supplying and fixing of following items in HT Panel. a. 230V AC 80/100 Wats Space Heaters | 24 | nos | sdee_sgd_bsnl | 365 |
| 9 | Heavy duty stem Type Safety Thermostat | b. Heavy duty stem Type Safety Thermostat | 24 | nos | sdee_sgd_bsnl | 365 |
| 10 | 6 Amps DP MCB | c. 6 Amps DP MCB including wiring for Heaters and Thermostats | 8 | nos | sdee_sgd_bsnl | 365 |
| 11 | Supply and wiring of 2.5 sqmm copper wire | d. Supply and wiring of 2.5 sqmm copper wire for heaters | 200 | mtrs | sdee_sgd_bsnl | 365 |
| 12 | 2core x1.5 sqmm Copper Armoured Cable | e. 2core x1.5 sqmm Copper Armoured Cable | 200 | mtrs | sdee_sgd_bsnl | 365 |
| 13 | Monoplast sealings for all HT terminations | f. Monoplast sealings for all HT terminations and Bus Joints in Bus chamber | 48 | mtrs | sdee_sgd_bsnl | 365 |
| 14 | General servicing of ACB in the MV panel | General servicing of existing 800/1000A capacity ACB in the MV panel, cleaning of contacts with CTC(carbon tetra chloride chemical), checking of trip bridges, shunt trip, UV coil, applying oil and grease for moving contacts checking of interconnections from the IDMT relay to ACB and other minor connected works | 54 | jobs | sdee_sgd_bsnl | 365 |
| 15 | General servicing of MV panel | General servicing of MV panel, Essential Panels, Power room panel, capacitor panel by checking for any loose wires, contacts, tightening the link bolts, checking of overheating of any wires, links rectifying the defects if any, cleaning the complete panel with blower to remove the dust etc., as required. | 20 | jobs | sdee_sgd_bsnl | 365 |
| 16 | Cleaning of HT Yard | Cleaning of HT Yard by removing of gross, trees, tree branches at SS yard surroundings etc., as required | 11 | jobs | sdee_sgd_bsnl | 365 |
| 17 | General servicing of existing Air Break switch | General servicing of existing 11KV, 400 Amps, 3 pole Gang operated type Air Break switch including cleaning of contacts replacing of metal parts if any burnt-out, checking of alignment for 3poles, applying of oil and grease, making free operation as reqrd., | 16 | jobs | sdee_sgd_bsnl | 365 |
| 18 | 63 Amps 3P MCB for Capacitors | Supplying and fixing of following accessories suitable for operation on 415volts three phase, 50Hz, AC supply and fixing in same in the existing panel including providing internal connections etc., as required. a. 63 Amps 3P MCB for Capacitors | 16 | nos | sdee_sgd_bsnl | 365 |
| 19 | 63 Amps HRC Fuse Links | b. 63 Amps HRC Fuse Links/bases | 16 | nos | sdee_sgd_bsnl | 365 |
| 20 | 6 Amps HRC Fuse Links | c. 6 Amps HRC Fuse Links | 40 | nos | sdee_sgd_bsnl | 365 |
| 21 | LED indication lamps | d. LED indication lamps | 40 | nos | sdee_sgd_bsnl | 365 |
| 22 | 20 KVAR Capacitor | e. 20 KVAR Capacitor | 6 | nos | sdee_sgd_bsnl | 365 |
| 23 | 10 KVAR Capacitor | f. 10 KVAR Capacitor | 6 | nos | sdee_sgd_bsnl | 365 |
| 24 | 5 KVAR Capacitor | g. 5 KVAR Capacitor | 6 | nos | sdee_sgd_bsnl | 365 |
| 25 | 96 x 96 mm Digital Ammeter | Supply and fixing of 96 x 96 mm Digital Ammeter / Voltmeter in existing MV panel by removing of faulty including mounting plate to suitable of existing 144 x 144 mm meters etc., as reqd., | 6 | jobs | sdee_sgd_bsnl | 365 |
| 26 | 95 Sqmm XLPE HT Cable | Supplying and laying of 3 Core 95 Sqmm XLPE HT Cable suitable for 11KV Voltage in the existing RCC/ HUME/ METAL pipe/Masonry duct as required. etc as required. | 60 | mtrs | sdee_sgd_bsnl | 365 |
| 27 | Heat Shrinkable joint kit | Supplying and making out door/Indoor type End termination with Heat Shrinkable joint kit to the existing 3 core 95 Sq. mm X L P E, 11KV H.T. cable including crimping of lugs, Providing cable supporting clamps, testing etc as required. (Raychem or SS make) | 12 | jobs | sdee_sgd_bsnl | 365 |
| 28 | Testing of the existing IDMT relay | Testing of the existing IDMT relay by primary injection method and secondary injection method and adjusting the relay setting as per the exchange load, submitting the test reports to the engineer in charge etc as required. | 20 | jobs | sdee_sgd_bsnl | 365 |
| 29 | Testing of earth pits | Testing of earth pits with Earth Tester, cleaning and painting of earth pit manhole chamber with white wash, improving of earth value by pouring salt water where ever needed ,checking of the earth connectivity from earth electrode to equipment connected and making good the same , tightening the loose connections and by replacing the new bolts and nuts brazing joints if needed. Submitting the earth value report to the engineer in charge etc., as required. | 50 | jobs | sdee_sgd_bsnl | 365 |
| 30 | Supply and fixing of 11 KV grade post top or pin Insulator | Supply and fixing of 11 KV grade post top/pin Insulator including replacing of faulty Insulators as reqd., | 50 | jobs | sdee_sgd_bsnl | 365 |
| 31 | Supplying and fixing of 9KV ,5KA rating Lightning arresters | Supplying and fixing of 9KV ,5KA rating Lightning arresters suitable for 11KV HT supply including testing at site making good etc as required | 20 | jobs | sdee_sgd_bsnl | 365 |
Experience Criteria
Past Performance
Bidder Turnover
Certificate (Requested in ATC)
OEM Authorization Certificate
OEM Annual Turnover *In case any bidder is seeking exemption from Experience / Turnover Criteria
the supporting documents to prove his eligibility for exemption must be uploaded for evaluation by the buyer
| S.No | Seller | Item | Date | Status |
|---|---|---|---|---|
| 1 | V S ELECTRICAL WORKS Under PMA | - | 09-08-2025 17:28:18 | Qualified |
| Rank | Seller | Price | Item |
|---|---|---|---|
| L1 | V S ELECTRICAL WORKS(MII) Under PMA | ₹21,13,700 | Item Categories : Attending emergency break down of HT services,Reconditioning of HT panel,Filtration of Transformer |
Sign up now to access all documents
Main Document
OTHER
BOQ
BOQ
ATC
GEM_GENERAL_TERMS_AND_CONDITIONS