Distribution Transformer, 3 Phase, 11 kV > 200 KVA up to and Including 2500 KVA
Tripura State Electricity Corporation Limited
WEST TRIPURA, TRIPURA
Menu
Bid Publish Date
09-Dec-2025, 11:39 am
Bid End Date
19-Dec-2025, 3:00 pm
EMD
₹10,000
Location
Progress
Quantity
1
Bid Type
Single Packet Bid
A tender has been published for Tamil Nadu Generation And Distribution Corporation Limited (tangedco) Distribution Transformer, 3 Phase, 11 kV > 200 KVA up to and Including 2500 KVA (Q3) in KANYAKUMARI, TAMIL NADU. Quantity: 1 by. Submission Deadline: 19-12-2025 15: 00: 00. Check eligibility and apply.
Tripura State Electricity Corporation Limited
WEST TRIPURA, TRIPURA
Bharat Petroleum Corporation Ltd
WEST DELHI, DELHI
Dedicated Freight Corridor Corporation Of India Limited
JAIPUR, RAJASTHAN
Bharat Petroleum Corporation Ltd
VADODARA, GUJARAT
N/a
SATARA, MAHARASHTRA
Tender Results
Loading results...
| Category | Specification | Requirement |
|---|---|---|
| STANDARDS | Energy efficiency level | 1 |
| STANDARDS | BEE Star Rating | 1 |
| STANDARDS | Installation, Testing and Demonstration | Yes . Including Civil work |
| STANDARDS | Minimum warranty on receipt of stores (in Months) | 66 |
| STANDARDS | Minimum warranty from the date of installation (in Months) | 60 |
| RATINGS | Nominal system voltage, HV ( in kV) | 11 |
| RATINGS | Nominal system voltage, LV ( in V) | 415 |
| RATINGS | Standard ratings (in kVA) | 250 |
| RATINGS | Minimum basic insulation level (in kVP) | 75 |
| RATINGS | No load voltage ratios (in Volts) | 11000/433-250 |
| RATINGS | Highest system voltage for equipment (in kV) | 12 |
| RATINGS | Rated lightning impulse withstand voltage (in kV Peak) (Refer IS:1180 (Part 1):2014 Annex-D) | 75 |
| CONSTRUCTION | Core mateial | CRGO (as per IS:3024 latest) |
| CONSTRUCTION | Conductor (Winding) material | Aluminium, Copper |
| CONSTRUCTION | Type of Mounting | Ground Mounted |
| CONSTRUCTION | Noise level at rated voltage and freqeuncy, Maximum (in dB) | 48 |
| TRANSFORMER TANK | Transformer tank cover construction | Sealed |
| TRANSFORMER TANK | Tank configuration with | Cooliong tubes |
| TRANSFORMER TANK | Material of transformer tank | Stainless steel |
| TRANSFORMER TANK | Minimum thickness of top and bottom material of transformer tank (in mm) | 7 |
| TRANSFORMER TANK | Minimum thickness of side material of transformer tank (in mm) | 5 |
| TRANSFORMER TANK | Material of Bolts/Nuts/Wahers exposed to atmosphere | Stainless steel (for upto 12 mm size), Brass (for upto 12 mm size), Electro Galvanized (for above 12 mm size), Hot Dip Galvanized (for above 12 mm size) |
| TRANSFORMER TANK | Gaskets wherever used shall conform to | Type III (as per IS:11149) Type C (as per IS:4253 (Pt.2) |
| TRANSFORMER TANK | Provision of conservator | No |
| Painting | Type of painting on inside of tank (hint: Refer Table 12 of IS:1180 (Pt.1):2014) | Oil resistant paint |
| Painting | Type of painting on External surface of tank (hint: Refer Table 12 of IS:1180 (Pt.1):2014) | Epoxy (Primer) |
| TAP CHANGER | Winding tapped | HV |
| TAP CHANGER | No. of positions (in Nos.) | 7 |
| TAP CHANGER | Voltage variation | +5% to -10% in steps of 2.5% for variation of HV |
| TERMINAL ARRANGEMENT | Transformer fitted with bushings of appropriate voltage and curent ratings on HV side | Yes. 3 Nos. (Conforming to IS:2099) |
| TERMINAL ARRANGEMENT | Transformer fitted with bushings of appropriate voltage and curent ratings on LV side | Yes. 4 Nos. (Conforming to IS:7421) |
| TERMINAL ARRANGEMENT | Suitable provision for adoption of cables of suitable size on LV side | Yes. For PVC/XLPE Cables |
| TERMINAL ARRANGEMENT | Cable End Box on HV side | Yes |
| TERMINAL ARRANGEMENT | Cable End Box on LV side | Yes |
| MARKING | Material of rating plate | Stainless steel |
| MARKING | Marking method on rating plate | Stamped |
| MARKING | Rating and terminal marking plates combined into one plate | Yes |
| OPTIONAL FITTINGS | Suitable rating lightning arrestors | HT Side, 1 No. per phase |
| OPTIONAL FITTINGS | Bird guard | Yes |
| OPTIONAL FITTINGS | Terminal connectors | Yes |
| OPTIONAL FITTINGS | Oil temperature indicator and widning temperature indicator | Yes |
| OPTIONAL FITTINGS | Jacking pads | No |
| OPTIONAL FITTINGS | Buchholz relay | NoMagnetic oil level gauge with low oil level alarm contact |
| OPTIONAL FITTINGS | Magnetic oil level gauge with low oil level alarm contact | Yes for transformer above 1600 |
| OPTIONAL FITTINGS | Non return valve | Yes |
| OPTIONAL FITTINGS | Protection relay for sealed type transformers for internal parameters that is pressure, temperature, oil level and gas detection | Yes |
| OPTIONAL FITTINGS | Unidirectional flat rollers | Yes |
| OPTIONAL FITTINGS | Drain cum sampling valve | Yes with steel plug (for transformers upto 500 KVA) |
| OPTIONAL FITTINGS | Self protection / disconnection devices | On secondary side (as per IS/IEC:60947-2:2003 |
| OPTIONAL FITTINGS | Expulsion fuse as disconnection device | No |
| SERVICE CONDITION | Maximum altitude | <1000 m |
| TEST REPORTS & CERTIFICATIONS | Availability of type test reports to prove the confirmity of the specification from | NABL Accrediated |
| TEST REPORTS & CERTIFICATIONS | Agreed for stage Inspection as required by buyer | Yes |
| SPECIAL TEST REPORTS | Availability of test report for Determination of sound level test | Yes |
| SPECIAL TEST REPORTS | Availability of test report for short circuit withstand test | Yes |
| SPECIAL TEST REPORTS | Availability of test report for No load current at 112.5 % Voltage | Yes |
| SPECIAL TEST REPORTS | Availability of test report for Paint adhesion test | Yes for 1 No. |
| SPECIAL TEST REPORTS | BDV and moisture content of oil in the transformer | Yes for 1 No. |
| SPECIAL TEST REPORTS | Other requirements | Limits of temeprature-rise as per Cl.7.10 of IS:1180 (Part 1):2014 latest |
Discover companies most likely to bid on this tender
Experience Criteria
Past Performance
Bidder Turnover
OEM Authorization Certificate
OEM Annual Turnover *In case any bidder is seeking exemption from Experience / Turnover Criteria
the supporting documents to prove his eligibility for exemption must be uploaded for evaluation by the buyer
Development Commissioner (micro Small & Medium Enterprises)
Controller General Of Patents Designs And Trade Marks (cgpdtm)
📍 AHMEDABAD, GUJARAT
Sign up now to access all documents
Main Document
CATALOG Specification
ATC
GEM_GENERAL_TERMS_AND_CONDITIONS
Choose from flexible plans to access tender documents instantly
Main Document
CATALOG Specification
ATC
GEM_GENERAL_TERMS_AND_CONDITIONS