Progress
Prasar Bharati Broadcasting Corporation Of India announces a tender for Supply of 11kV 3 phase, 630Amps, Motorized SCADA compatible Monitoring and Controlling, SF6 Insulated Outdoor, totally enclosed, 5Way Ring Main Unit RMU, Insurance, transportation and unloading of RMU at site, Design, fabrication and construction of RCC foundation or plinth for 5Way RMU panels, Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from 11kV Feeder structure to RMU panel, Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from Outdoor type RMU to 4 panel HT Switchgear, Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from 4 panel HT Switchgear to 500 kVA Transformers 2 Nos. , Supply and fixing of outdoor heat shrinkable end standard make termination kits for 11 kV, 120Sq mm XLPE HT Cable for RMU, Supply and fixing of indoor heat shrinkable or end standard make Cable termination kits for 11 kV, 120Sq mm XLPE HT Cable for HT Switchgear Panel and 500KVA Indoor Transformers 2 Nos. , Supply and fixing of indoor heat shrinkable or end standard make Cable termination kits for 11 kV 120Sq mm XLPE HT Cable 500KVA Indoor Transformers 2 Nos, Supply and Providing conventional type Copper plate earthing system for RMU, Excavation and Laying Copper strip from Earth pit terminal to the 5way RMU and Terminations as per TGSPDCL Hyderabad norms, Testing of High Voltage HT Cables, Provision for cable glands in RMU, and providing cable glands, lugs, ferrules, cable clamps and other termination accessories for HT cables. , System integration, trial run, and commissioning of complete 11kV power supply system including synchronization with existing network, Preparation and submission of as-built drawings, test certificates, O and M Manuals and commissioning reports and Towards charges for submission of RMU drawings to TGSPDCL, Hyderabad, Erection or Installation, testing and commissioning of 5 Way RMU units including obtaining approval from, TGSPDCL, Hyderabad Central Electricity Authorities. , Tripping battery system complete with trickle charger operating from 230V mains for use with the tripping circuit of above switch board if necessary, Any other material or work necessary to complete the SITC and Approval from CEA and any other Department in HYDERABAD, TELANGANA. Quantity: 132. Submission Deadline: 29-08-2026 12: 00: 00. Last date to apply is approaching fast!
Quantity
132
Category
Supply of 11kV 3 phase, 630Amps, Motorized SCADA compatible Monitoring and Controlling , SF6 Insulated Outdoor, totally enclosed, 5Way Ring Main Unit RMU
Bid Type
Two Packet Bid
Bid Validity
120 (Days)
Bid Type
Service
Evaluation
Total value wise evaluation
Inspection Required
No
RA Qualification Rule
H1-Highest Priced Bid Elimination
Tech Clarification Time
2 Days
EMD Required
Yes
MII Purchase Preference
Yes
MII Preference Band
L1+20%
MSE Purchase Preference
Yes
MSE Preference Band
L1+15%
MSE Exemption/Relaxation
No
Startup Exemption/Relaxation
No
Bid Splitting Applied
No
Min. Avg. Annual Turnover
32
Past Performance
80 %
Warranty Period
5 years
Experience Required
3 Year (s)
Arbitration Clause
No
Mediation Clause
No
Tender Category
Goods
Bid To RA
No
Bid To RA Enabled
Yes
Item Category
Supply of 11kV 3 phase, 630Amps, Motorized SCADA compatible Monitoring and Controlling , SF6 Insulated Outdoor, totally enclosed, 5Way Ring Main Unit RMU , Insurance, transportation and unloading of RMU at site , Design, fabrication and construction of RCC foundation or plinth for 5Way RMU panels , Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from 11kV Feeder structure to RMU panel , Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from Outdoor type RMU to 4 panel HT Switchgear , Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from 4 panel HT Switchgear to 500 kVA Transformers 2 Nos. , Supply and fixing of outdoor heat shrinkable end standard make termination kits for 11 kV, 120Sq mm XLPE HT Cable for RMU , Supply and fixing of indoor heat shrinkable or end standard make Cable termination kits for 11 kV, 120Sq mm XLPE HT Cable for HT Switchgear Panel and 500KVA Indoor Transformers 2 Nos. , Supply and fixing of indoor heat shrinkable or end standard make Cable termination kits for 11 kV 120Sq mm XLPE HT Cable 500KVA Indoor Transformers 2 Nos , Supply and Providing conventional type Copper plate earthing system for RMU , Excavation and Laying Copper strip from Earth pit terminal to the 5way RMU and Terminations as per TGSPDCL Hyderabad norms , Testing of High Voltage HT Cables , Provision for cable glands in RMU, and providing cable glands, lugs, ferrules, cable clamps and other termination accessories for HT cables. , System integration, trial run, and commissioning of complete 11kV power supply system including synchronization with existing network , Preparation and submission of as-built drawings, test certificates, O and M Manuals and commissioning reports and Towards charges for submission of RMU drawings to TGSPDCL, Hyderabad , Erection or Installation, testing and commissioning of 5 Way RMU units including obtaining approval from, TGSPDCL ,Hyderabad Central Electricity Authorities. , Tripping battery system complete with trickle charger operating from 230V mains for use with the tripping circuit of above switch board if necessary , Any other material or work necessary to complete the SITC and Approval from CEA and any other Department
Advisory Bank
State Bank of India
ePBG Percentage
3%
ePBG Duration (Months)
62
Max Delivery Days
60
Delivery Locations
1
Delivery Cities
Medchal Malkajgiri
Delivery Pincodes
500013
| Consignee | Address | City | State | Pincode | Quantity | Delivery Days | Additional Requirement |
|---|---|---|---|---|---|---|---|
| Banavatu Srinivasarao | 500013,Doordarshan Kendra Ramanthapur Hyderabad 500013 | Medchal Malkajgiri | Telangana | 500013 | 1 | 60 | - |
End-to-end support — bid preparation, GeM registration, document filing & compliance by industry experts.
Free consultation · 24h response
Main Document
OTHER
BOQ
BOQ
GEM_GENERAL_TERMS_AND_CONDITIONS
Supply of 11kV 3 phase, 630Amps, Motorized SCADA compatible Monitoring and Controlling , SF6 Insulated Outdoor, totally enclosed, 5Way Ring Main Unit RMU
Supply of 11kV 3 phase, 630Amps, Motorized SCADA compatible Monitoring and Controlling , SF6 Insulated Outdoor, totally enclosed, 5Way Ring Main Unit RMU Consisting of Incoming LBS 2 Nos and Outgoing CB 3 Nos. with voltage and current Metering on all incoming or Outgoing feeders including all the protective devices confirming to standard IS3427 1997 amended to date as detailed below and conforming to TGSPDCTL ,Hyderabad requirements. RMU design and CT PT ratio should be suitable for 320kVA Maximum Demand.
Insurance, transportation and unloading of RMU at site
Insurance, transportation and unloading of RMU at site
Design, fabrication and construction of RCC foundation or plinth for 5Way RMU panels
Design, fabrication and construction of RCC foundation / plinth for 5Way RMU panels including anchor bolts, cable trench interface panel to panel and civil works as recommended by OEM and as per TGSPDCL Hyderabad norms.
Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from 11kV Feeder structure to RMU panel
Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from 11kV Feeder structure to Outdoor type RMU incomer panel. Work includes excavation of cable trench, laying of HT Cable, filling with sand cushioning, bricks and closing with protective covers trench, providing cable markers and back filling as per TGSPDCL ,Hyderabad norms. Payment shall be as per actuals
Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from Outdoor type RMU to 4 panel HT Switchgear
Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from Outdoor type RMU to 4 Panel HT Switchgear Work includes excavation of cable trench, laying of HT Cable, filling with sand cushioning, bricks and closing with protective covers trench, providing cable markers and back filling as per TGSPDCL ,Hyderabad norms. Payment shall be as per actuals
Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from 4 panel HT Switchgear to 500 kVA Transformers 2 Nos.
Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from 4 Panel HT Switchgear to 500 kVA Transformers 2 Nos. Work includes excavation of cable trench, laying of HT Cable, filling with sand cushioning, bricks and closing with protective covers trench, providing cable markers and back filling as per TGSPDCLTL ,Hyderabad norms. Payment shall be as per actuals.
Supply and fixing of outdoor heat shrinkable end standard make termination kits for 11 kV, 120Sq mm XLPE HT Cable for RMU
Supply and fixing of outdoor heat shrinkable / end standard make termination kits for 11 kV, 120Sq mm XLPE HT Cable for RMU
Supply and fixing of indoor heat shrinkable or end standard make Cable termination kits for 11 kV, 120Sq mm XLPE HT Cable for HT Switchgear Panel and 500KVA Indoor Transformers 2 Nos.
Supply and fixing of indoor heat shrinkable or end standard make Cable termination kits for 11 kV, 120Sq mm XLPE HT Cable for HT Switchgear Panel and 500KVA Indoor Transformers 2 Nos
Supply and fixing of indoor heat shrinkable or end standard make Cable termination kits for 11 kV 120Sq mm XLPE HT Cable 500KVA Indoor Transformers 2 Nos
Supply and fixing of indoor heat shrinkable or end standard make Cable termination kits for 11 kV 120Sq mm XLPE HT Cable 500KVA Indoor Transformers 2 Nos
Supply and Providing conventional type Copper plate earthing system for RMU
Supply and Providing conventional type Copper plate earthing system for RMU including termination, interconnections, test links and all accessories as per the drawing enclosed in Annexure C Diagram 2 for completion of the earthing.Copper Strips 50 x 3 mm As per Actuals, Copper Plate, GI Pipe,and any other required materials to complete the Earthing system should be supplied by the tenderer. Copper Purity Certificate for 99.95 Percentage to be submitted for the copper materials supplied for Earthing system.
Excavation and Laying Copper strip from Earth pit terminal to the 5way RMU and Terminations as per TGSPDCL Hyderabad norms
Excavation and Laying Copper strip from Earth pit terminal to the 5way RMU and terminations as per TGSPDCL, Hyderabad Norms . Payment shall be as per actuals at the Site
Testing of High Voltage HT Cables
Testing of High Voltage HT Cables including insulation resistance, continuity and sheath integrity before laying of cable
Provision for cable glands in RMU, and providing cable glands, lugs, ferrules, cable clamps and other termination accessories for HT cables.
Provision for cable glands in RMU, and providing cable glands, lugs, ferrules, cable clamps and other termination accessories for HT cables.
System integration, trial run, and commissioning of complete 11kV power supply system including synchronization with existing network
System integration, trial run, and commissioning of complete 11kV power supply system including synchronization with existing network
Preparation and submission of as-built drawings, test certificates, O and M Manuals and commissioning reports and Towards charges for submission of RMU drawings to TGSPDCL, Hyderabad
Preparation and submission of as-built drawings, test certificates, O and M Manuals and commissioning reports and Towards charges for submission of RMU drawings to TGSPDCL, Hyderabad
Erection or Installation, testing and commissioning of 5 Way RMU units including obtaining approval from, TGSPDCL ,Hyderabad Central Electricity Authorities.
Erection/Installation, testing and commissioning of 5 Way RMU units including obtaining approval from, TGSPDCL ,Hyderabad / Central Electricity Authorities.
Tripping battery system complete with trickle charger operating from 230V mains for use with the tripping circuit of above switch board if necessary
Tripping battery system complete with trickle charger operating from 230V mains for use with the tripping circuit of above switch board ( if necessary)
Any other material or work necessary to complete the SITC and Approval from CEA and any other Department
Any other material/work necessary to complete the SITC and Approval from CEA and any other Department
| Item # | Title | Description | Quantity | Unit | Consignee | Delivery (Days) | Price Trends |
|---|---|---|---|---|---|---|---|
| 1 | Supply of 11kV 3 phase, 630Amps, Motorized SCADA compatible Monitoring and Controlling , SF6 Insulated Outdoor, totally enclosed, 5Way Ring Main Unit RMU | Supply of 11kV 3 phase, 630Amps, Motorized SCADA compatible Monitoring and Controlling , SF6 Insulated Outdoor, totally enclosed, 5Way Ring Main Unit RMU Consisting of Incoming LBS 2 Nos and Outgoing CB 3 Nos. with voltage and current Metering on all incoming or Outgoing feeders including all the protective devices confirming to standard IS3427 1997 amended to date as detailed below and conforming to TGSPDCTL ,Hyderabad requirements. RMU design and CT PT ratio should be suitable for 320kVA Maximum Demand. | 1 | set | dde_ddkhyd | 30 | |
| 2 | Insurance, transportation and unloading of RMU at site | Insurance, transportation and unloading of RMU at site | 1 | job | dde_ddkhyd | 30 | |
| 3 | Design, fabrication and construction of RCC foundation or plinth for 5Way RMU panels | Design, fabrication and construction of RCC foundation / plinth for 5Way RMU panels including anchor bolts, cable trench interface panel to panel and civil works as recommended by OEM and as per TGSPDCL Hyderabad norms. | 1 | job | dde_ddkhyd | 30 | |
| 4 | Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from 11kV Feeder structure to RMU panel | Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from 11kV Feeder structure to Outdoor type RMU incomer panel. Work includes excavation of cable trench, laying of HT Cable, filling with sand cushioning, bricks and closing with protective covers trench, providing cable markers and back filling as per TGSPDCL ,Hyderabad norms. Payment shall be as per actuals | 20 | mtr | dde_ddkhyd | 30 | |
| 5 | Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from Outdoor type RMU to 4 panel HT Switchgear | Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from Outdoor type RMU to 4 Panel HT Switchgear Work includes excavation of cable trench, laying of HT Cable, filling with sand cushioning, bricks and closing with protective covers trench, providing cable markers and back filling as per TGSPDCL ,Hyderabad norms. Payment shall be as per actuals | 40 | mtr | dde_ddkhyd | 30 | |
| 6 | Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from 4 panel HT Switchgear to 500 kVA Transformers 2 Nos. | Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from 4 Panel HT Switchgear to 500 kVA Transformers 2 Nos. Work includes excavation of cable trench, laying of HT Cable, filling with sand cushioning, bricks and closing with protective covers trench, providing cable markers and back filling as per TGSPDCLTL ,Hyderabad norms. Payment shall be as per actuals. | 20 | mtr | dde_ddkhyd | 30 | |
| 7 | Supply and fixing of outdoor heat shrinkable end standard make termination kits for 11 kV, 120Sq mm XLPE HT Cable for RMU | Supply and fixing of outdoor heat shrinkable / end standard make termination kits for 11 kV, 120Sq mm XLPE HT Cable for RMU | 10 | nos | dde_ddkhyd | 30 | |
| 8 | Supply and fixing of indoor heat shrinkable or end standard make Cable termination kits for 11 kV, 120Sq mm XLPE HT Cable for HT Switchgear Panel and 500KVA Indoor Transformers 2 Nos. | Supply and fixing of indoor heat shrinkable or end standard make Cable termination kits for 11 kV, 120Sq mm XLPE HT Cable for HT Switchgear Panel and 500KVA Indoor Transformers 2 Nos | 8 | nos | dde_ddkhyd | 30 | |
| 9 | Supply and fixing of indoor heat shrinkable or end standard make Cable termination kits for 11 kV 120Sq mm XLPE HT Cable 500KVA Indoor Transformers 2 Nos | Supply and fixing of indoor heat shrinkable or end standard make Cable termination kits for 11 kV 120Sq mm XLPE HT Cable 500KVA Indoor Transformers 2 Nos | 2 | nos | dde_ddkhyd | 30 | |
| 10 | Supply and Providing conventional type Copper plate earthing system for RMU | Supply and Providing conventional type Copper plate earthing system for RMU including termination, interconnections, test links and all accessories as per the drawing enclosed in Annexure C Diagram 2 for completion of the earthing.Copper Strips 50 x 3 mm As per Actuals, Copper Plate, GI Pipe,and any other required materials to complete the Earthing system should be supplied by the tenderer. Copper Purity Certificate for 99.95 Percentage to be submitted for the copper materials supplied for Earthing system. | 2 | sets | dde_ddkhyd | 30 | |
| 11 | Excavation and Laying Copper strip from Earth pit terminal to the 5way RMU and Terminations as per TGSPDCL Hyderabad norms | Excavation and Laying Copper strip from Earth pit terminal to the 5way RMU and terminations as per TGSPDCL, Hyderabad Norms . Payment shall be as per actuals at the Site | 20 | mtr | dde_ddkhyd | 30 | |
| 12 | Testing of High Voltage HT Cables | Testing of High Voltage HT Cables including insulation resistance, continuity and sheath integrity before laying of cable | 1 | job | dde_ddkhyd | 30 | |
| 13 | Provision for cable glands in RMU, and providing cable glands, lugs, ferrules, cable clamps and other termination accessories for HT cables. | Provision for cable glands in RMU, and providing cable glands, lugs, ferrules, cable clamps and other termination accessories for HT cables. | 1 | lumpsum | dde_ddkhyd | 30 | |
| 14 | System integration, trial run, and commissioning of complete 11kV power supply system including synchronization with existing network | System integration, trial run, and commissioning of complete 11kV power supply system including synchronization with existing network | 1 | job | dde_ddkhyd | 30 | |
| 15 | Preparation and submission of as-built drawings, test certificates, O and M Manuals and commissioning reports and Towards charges for submission of RMU drawings to TGSPDCL, Hyderabad | Preparation and submission of as-built drawings, test certificates, O and M Manuals and commissioning reports and Towards charges for submission of RMU drawings to TGSPDCL, Hyderabad | 1 | job | dde_ddkhyd | 30 | |
| 16 | Erection or Installation, testing and commissioning of 5 Way RMU units including obtaining approval from, TGSPDCL ,Hyderabad Central Electricity Authorities. | Erection/Installation, testing and commissioning of 5 Way RMU units including obtaining approval from, TGSPDCL ,Hyderabad / Central Electricity Authorities. | 1 | job | dde_ddkhyd | 30 | |
| 17 | Tripping battery system complete with trickle charger operating from 230V mains for use with the tripping circuit of above switch board if necessary | Tripping battery system complete with trickle charger operating from 230V mains for use with the tripping circuit of above switch board ( if necessary) | 1 | set | dde_ddkhyd | 30 | |
| 18 | Any other material or work necessary to complete the SITC and Approval from CEA and any other Department | Any other material/work necessary to complete the SITC and Approval from CEA and any other Department | 1 | lumpsum | dde_ddkhyd | 30 |
Extended Deadline
29-Aug-2026, 6:30 am
Opening Date
29-Aug-2026, 7:00 am
Extended Deadline
24-Aug-2026, 6:30 am
Opening Date
24-Aug-2026, 7:00 am
Experience Criteria
Past Performance
Bidder Turnover
Certificate (Requested in ATC)
OEM Authorization Certificate
Additional Doc 1 (Requested in ATC)
Compliance of BoQ specification and supporting document *In case any bidder is seeking exemption from Experience / Turnover Criteria
the supporting documents to prove his eligibility for exemption must be uploaded for evaluation by the buyer