Bhakra Beas Management Board invites bids for Distribution Transformer, 3 Phase, 11 kV > 200 KVA up to and Including 2500 KVA (Q3) in KANGRA, HIMACHAL PRADESH. Quantity: 3. Submission Deadline: 23-10-2025 18: 00: 00. Submit your proposal before the deadline.
Tender Category
Goods
Bid To RA
No
Bid To RA Enabled
Yes
Item Category
Distribution Transformer, 3 Phase, 11 kV > 200 KVA up to and Including 2500 KVA (Q3)
End-to-end support — bid preparation, GeM registration, document filing & compliance by industry experts.
Free consultation · 24h response
Main Document
CATALOG Specification
GEM_GENERAL_TERMS_AND_CONDITIONS
| Category | Specification | Requirement |
|---|---|---|
| STANDARDS | Energy efficiency level | 2 |
| STANDARDS | BEE Star Rating | 1 |
| STANDARDS | Installation, Testing and Demonstration | No |
| STANDARDS | Minimum warranty on receipt of stores (in Months) | 30 |
| STANDARDS | Minimum warranty from the date of installation (in Months) | 24 |
| RATINGS | Nominal system voltage, HV ( in kV) | 11 |
| RATINGS | Nominal system voltage, LV ( in V) | 415 |
| RATINGS | Standard ratings (in kVA) | 500 |
| RATINGS | Minimum basic insulation level (in kVP) | 75 |
| RATINGS | No load voltage ratios (in Volts) | 11000/433-250 |
| RATINGS | Highest system voltage for equipment (in kV) | 12 |
| RATINGS | Rated lightning impulse withstand voltage (in kV Peak) (Refer IS:1180 (Part 1):2014 Annex-D) | 75 |
| CONSTRUCTION | Core mateial | CRGO (as per IS:3024 latest) |
| CONSTRUCTION | Conductor (Winding) material | Copper |
| CONSTRUCTION | Vector Group | Dyn-11 |
| CONSTRUCTION | Type of Mounting | Ground Mounted |
| CONSTRUCTION | Noise level at rated voltage and freqeuncy, Maximum (in dB) | 55 |
| TRANSFORMER TANK | Transformer tank cover construction | Non-sealed, Bolted |
| TRANSFORMER TANK | Tank configuration with | With radiator fins |
| TRANSFORMER TANK | Material of transformer tank | Mild Steel |
| TRANSFORMER TANK | Minimum thickness of top and bottom material of transformer tank (in mm) | 6 |
| TRANSFORMER TANK | Minimum thickness of side material of transformer tank (in mm) | 4 |
| TRANSFORMER TANK | Material of Bolts/Nuts/Wahers exposed to atmosphere | Stainless steel (for upto 12 mm size), Brass (for upto 12 mm size), Electro Galvanized (for above 12 mm size), Hot Dip Galvanized (for above 12 mm size) |
| TRANSFORMER TANK | Gaskets wherever used shall conform to | Type III (as per IS:11149) Type C (as per IS:4253 (Pt.2) |
| TRANSFORMER TANK | Provision of conservator | Yes , for Non sealed type with Plain tank construction |
| Painting | Type of painting on inside of tank (hint: Refer Table 12 of IS:1180 (Pt.1):2014) | Oil resistant paint |
| Painting | Type of painting on External surface of tank (hint: Refer Table 12 of IS:1180 (Pt.1):2014) | Epoxy (Primer) |
| TAP CHANGER | Winding tapped | HV |
| TAP CHANGER | No. of positions (in Nos.) | 7 |
| TAP CHANGER | Voltage variation | +5% to -10% in steps of 2.5% for variation of HV |
| TERMINAL ARRANGEMENT | Transformer fitted with bushings of appropriate voltage and curent ratings on HV side | Yes. 3 Nos. (Conforming to IS:2099) |
| TERMINAL ARRANGEMENT | Transformer fitted with bushings of appropriate voltage and curent ratings on LV side | Yes. 4 Nos. (Conforming to IS:7421) |
| TERMINAL ARRANGEMENT | Suitable provision for adoption of cables of suitable size on LV side | Yes. For PVC/XLPE Cables |
| TERMINAL ARRANGEMENT | Cable End Box on HV side | No |
| TERMINAL ARRANGEMENT | Cable End Box on LV side | Yes, No |
| MARKING | Material of rating plate | Stainless steel |
| MARKING | Marking method on rating plate | Engraved |
| MARKING | Rating and terminal marking plates combined into one plate | No |
| OPTIONAL FITTINGS | Suitable rating lightning arrestors | HT Side, 1 No. per phase |
| OPTIONAL FITTINGS | Bird guard | No |
| OPTIONAL FITTINGS | Terminal connectors | No |
| OPTIONAL FITTINGS | Oil temperature indicator and widning temperature indicator | Yes |
| OPTIONAL FITTINGS | Jacking pads | Yes for transformer above 1600 KVA, No, Yes |
| OPTIONAL FITTINGS | Buchholz relay | Yes, NoMagnetic oil level gauge with low oil level alarm contact |
| OPTIONAL FITTINGS | Magnetic oil level gauge with low oil level alarm contact | Yes |
| OPTIONAL FITTINGS | Non return valve | Yes |
| OPTIONAL FITTINGS | Protection relay for sealed type transformers for internal parameters that is pressure, temperature, oil level and gas detection | No |
| OPTIONAL FITTINGS | Unidirectional flat rollers | Yes |
| OPTIONAL FITTINGS | Drain cum sampling valve | Yes |
| OPTIONAL FITTINGS | Self protection / disconnection devices | No |
| OPTIONAL FITTINGS | Expulsion fuse as disconnection device | No |
| SERVICE CONDITION | Maximum altitude | <1000 m |
| TEST REPORTS & CERTIFICATIONS | Availability of type test reports to prove the confirmity of the specification from | NABL Accrediated |
| TEST REPORTS & CERTIFICATIONS | Agreed for stage Inspection as required by buyer | Yes |
| SPECIAL TEST REPORTS | Availability of test report for Determination of sound level test | Yes |
| SPECIAL TEST REPORTS | Availability of test report for short circuit withstand test | Yes |
| SPECIAL TEST REPORTS | Availability of test report for No load current at 112.5 % Voltage | Yes |
| SPECIAL TEST REPORTS | Availability of test report for Paint adhesion test | Yes for all units |
| SPECIAL TEST REPORTS | BDV and moisture content of oil in the transformer | Yes for all units |
| SPECIAL TEST REPORTS | Other requirements | Losses and Impedance values as per Cl.7.8 and Table 6 of IS:1180 (Part 1):2014 latest, Limits of temeprature-rise as per Cl.7.10 of IS:1180 (Part 1):2014 latest |
Experience Criteria
Past Performance
Bidder Turnover
Certificate (Requested in ATC)
OEM Authorization Certificate
OEM Annual Turnover *In case any bidder is seeking exemption from Experience / Turnover Criteria
the supporting documents to prove his eligibility for exemption must be uploaded for evaluation by the buyer
Start
30-Oct-2025, 4:00 pm
End
05-Nov-2025, 3:48 pm
Duration: 144 hours
Reverse Auction Document
✅ RA concluded. Check financial results for final rankings.
| S.No | Seller | Item | Date | Status |
|---|---|---|---|---|
| 1 | ABC TRANSFORMERS PRIVATE LIMITED Under PMA | Make : ABC TRANSFORMERS Model : ABC500KVA11KVEELL2 | 23-10-2025 16:38:00 | |
| 2 | MIRZAPUR ELECTRICAL INDUSTRIES LTD. Under PMA | Make : AGROSONS Model : 500 KVA, 11 /0.433 kv TRANSFORMER | 23-10-2025 13:04:00 | |
| 3 | POWER STAR Under PMA | Make : POWERSTAR Model : PS/500KVA | 23-10-2025 17:08:36 |
These are the final prices after the reverse auction event. Prices may be lower than initial bids.
| Rank | Seller | Final Price | Item |
|---|---|---|---|
| L1 | POWER STAR(MSE,MII) Under PMA Winner | ₹26,90,568 | Item Categories : Distribution Transformer, 3 Phase, 11 kV > 200 KVA up to and Including 2500 KVA |
| L2 | MIRZAPUR ELECTRICAL INDUSTRIES LTD. (MSE,MII) Under PMA | ₹26,91,000 | Item Categories : Distribution Transformer, 3 Phase, 11 kV > 200 KVA up to and Including 2500 KVA |
| L3 | ABC TRANSFORMERS PRIVATE LIMITED (MII) Under PMA | ₹42,38,214 | Item Categories : Distribution Transformer, 3 Phase, 11 kV > 200 KVA up to and Including 2500 KVA |
🎉 L1 Winner
POWER STAR(MSE,MII) Under PMA
Final Price: ₹26,90,568
Please sign in or create an account to view contract details and download result documents.
Sign up now to access all documents
Main Document
CATALOG Specification
GEM_GENERAL_TERMS_AND_CONDITIONS