Indian Army XLPE Cable & LED Luminaire Tender 2026 India IS 7098 IS 10322 ISI AAA/TRTL
Indian Army
Rangareddi, TELANGANA
Bid Publish Date
09-Feb-2026, 5:11 pm
Bid End Date
19-Feb-2026, 6:00 pm
Progress
Quantity
1
Bid Type
Single Packet Bid
Modern Coach Factory Raebareli has released a public tender for Distribution Transformer, 3 Phase, Up to and including 200 KVA (Q3). Quantity: 1. Submission Deadline: 19-02-2026 18: 00: 00. Download documents and apply online.
Main Document
CATALOG Specification
GEM_GENERAL_TERMS_AND_CONDITIONS
Indian Army
Rangareddi, TELANGANA
Indian Army
KAMRUP, ASSAM
Indian Air Force
JAISALMER, RAJASTHAN
Indian Army
CHENNAI, TAMIL NADU
Indian Army
JALANDHAR, PUNJAB
Tender Results
Loading results...
| Category | Specification | Requirement |
|---|---|---|
| STANDARDS | Energy efficiency level | 1 |
| STANDARDS | BEE Star Rating | 1, 2, 3, 4, 5 Or higher |
| STANDARDS | Installation, Testing and Demonstration | No |
| STANDARDS | Minimum warranty (in Months) on receipt of stores, irrespective of the date of installation | 66, 78, 60 Or higher |
| STANDARDS | Minimum warranty (in Months) from the date of installation (Note: If "0" is selected, "Minimum warranty (in Months) on receipt of stores" shall still be applicable irrespective of the date of installation | 0 |
| RATINGS | Nominal system voltage, HV ( in kV) | 11 |
| RATINGS | Nominal system voltage, LV ( in V) | 433 |
| RATINGS | Standard ratings (in kVA) | 63 |
| RATINGS | Minimum basic insulation level (in kVP) | 75 |
| RATINGS | No load voltage ratios (in Volts) | 11000/433-250 |
| RATINGS | Highest system voltage for equipment (in kV) | 12 |
| RATINGS | Rated lightning impulse withstand voltage (in kV Peak) (Refer IS:1180 (Part 1):2014 Annex-D) | 75 |
| CONSTRUCTION | Core mateial | CRGO (as per IS:3024 latest) |
| CONSTRUCTION | Conductor (Winding) material | Copper |
| CONSTRUCTION | Type of Mounting | Pole Mounted |
| CONSTRUCTION | Method of system earthing | solidly earthed |
| CONSTRUCTION | Noise level at rated voltage and freqeuncy, Maximum (in dB) | 51 |
| TRANSFORMER TANK | Transformer tank cover construction | Non-sealed, Bolted |
| TRANSFORMER TANK | Tank configuration with | With radiator fins |
| TRANSFORMER TANK | Material of transformer tank | Mild Steel |
| TRANSFORMER TANK | Minimum thickness of top and bottom material of transformer tank (in mm) | 5 |
| TRANSFORMER TANK | Minimum thickness of side material of transformer tank (in mm) | 4 |
| TRANSFORMER TANK | Material of Bolts/Nuts/Wahers exposed to atmosphere | Stainless steel (for upto 12 mm size), Electro Galvanized (for above 12 mm size) |
| TRANSFORMER TANK | Gaskets wherever used shall conform to | Type III (as per IS:11149) Type C (as per IS:4253 (Pt.2) |
| TRANSFORMER TANK | Provision of conservator | Yes , for Non sealed type with Plain tank construction |
| PAINTING | Type of painting on inside of tank (hint: Refer Table 12 of IS:1180 (Pt.1):2014) | Hot oil resistant paint |
| PAINTING | Type of painting on External surface of tank | Epoxy (Primer), Polyurethane (finish coat) |
| TAP CHANGER | Tap changing arrangement | Not applicable |
| TAP CHANGER | Winding tapped | Not applicable |
| TAP CHANGER | No. of positions (in Nos.) | 0 |
| TAP CHANGER | Voltage variation | Not applicable |
| TERMINAL ARRANGEMENT | Transformer fitted with bushings of appropriate voltage and curent ratings on HV side | Yes. 3 Nos. (Conforming to IS:2099) |
| TERMINAL ARRANGEMENT | Transformer fitted with bushings of appropriate voltage and curent ratings on LV side | Yes. 5 Nos. (Conforming to IS:7421) |
| TERMINAL ARRANGEMENT | Suitable provision for adoption of cables of suitable size on LV side | Yes. For PVC/XLPE Cables |
| TERMINAL ARRANGEMENT | Cable End Box on HV side | No |
| TERMINAL ARRANGEMENT | Cable End Box on LV side | No |
| AIR CLEARANCE | Minimum air clearances in cable box | as per Table 11 of IS:1180 (Part 1):2014 latest, Without cable box |
| AIR CLEARANCE | Suitable bimetallic connectors (clamp type) shall be provided on both HV and LV side in order to ensure sound and robust connection | Yes. For Bare bushing termination |
| MARKING | Material of rating plate | Anodized aluminium |
| MARKING | Marking method on rating plate | Engraved |
| MARKING | Rating and terminal marking plates combined into one plate | Yes |
| OPTIONAL FITTINGS | Dehydrating breather in lieu of plain breathing device for transformers | Yes |
| OPTIONAL FITTINGS | Filter Valve for transformers | Yes |
| OPTIONAL FITTINGS | Suitable rating lightning arrestors | No |
| OPTIONAL FITTINGS | Bird guard | No |
| OPTIONAL FITTINGS | Terminal connectors | Yes |
| OPTIONAL FITTINGS | Non return valve | No |
| OPTIONAL FITTINGS | Pressure relief device or explosion vent (upto 200 KVA doe non-sealed type transformer) | Yes |
| OPTIONAL FITTINGS | Protection relay for sealed type transformers for internal parameters that is pressure, temperature, oil level and gas detection | No |
| OPTIONAL FITTINGS | Anti-theft stainless steel fasteners with breakway nut at top cover (upto 200 KVA) | No |
| OPTIONAL FITTINGS | Drain cum sampling valve | Yes with steel plug |
| OPTIONAL FITTINGS | Self protection / disconnection devices | No |
| OPTIONAL FITTINGS | Expulsion fuse as disconnection device | No |
| SERVICE CONDITION | Maximum altitude | <1000 m |
| TEST REPORTS & CERTIFICATIONS | Availability of type test reports to prove the confirmity of the specification from | NABL Accrediated |
| SPECIAL TEST REPORTS | Availability of test report for Determination of sound level test | No |
| SPECIAL TEST REPORTS | Availability of test report for No load current at 112.5 % Voltage | Yes |
| SPECIAL TEST REPORTS | Availability of test report for Paint adhesion test | No |
| SPECIAL TEST REPORTS | BDV and moisture content of oil in the transformer | No |
| SPECIAL TEST REPORTS | Other requirements | Losses and Impedance values as per Cl.6.8 and Table 3 of IS:1180 (Part 1):2014 latest, Limits of temepraturerise as per Cl.6.10 of IS:1180 (Part 1):2014 latest, Short circuit withstand test, Lightning impulse test as per IS:1180, Pressure test as per IS:1180 |
Discover companies most likely to bid on this tender
Certificate (Requested in ATC)
OEM Authorization Certificate *In case any bidder is seeking exemption from Experience / Turnover Criteria
the supporting documents to prove his eligibility for exemption must be uploaded for evaluation by the buyer
E-municipalities - Eservices To Citizens And Employees Of Urban Local Bodies Of Uttar Pradesh
📍 MAHARAJGANJ, UTTAR PRADESH
Nlc India Limited
📍 CUDDALORE, TAMIL NADU
Uranium Corporation Of India Limited
📍 EAST SINGHBHUM, JHARKHAND
Bharat Electronics Limited (bel)
📍 BANGALORE, KARNATAKA
Bharat Heavy Electricals Limited (bhel)
📍 TUTICORIN, TAMIL NADU
Sign up now to access all documents
Main Document
CATALOG Specification
GEM_GENERAL_TERMS_AND_CONDITIONS