Rural Development And Panchayat Raj Department Maharashtra White LED Solar Street Lighting System Tender 2026 Bhandara MAHA
N/a
BHANDARA, MAHARASHTRA
Bid Publish Date
04-Feb-2026, 12:35 pm
Bid End Date
19-Feb-2026, 12:00 pm
EMD
₹1,35,000
Value
₹45,00,000
Location
Progress
Quantity
10
Bid Type
Two Packet Bid
Commissionerate Of Schools has released a public tender for Solar Power Plant (Roof Top) for ONGRID System, Single Phase (Q3) in PANCH MAHALS, GUJARAT. Quantity: 10. Submission Deadline: 19-02-2026 12: 00: 00. Download documents and apply online.
Main Document
CATALOG Specification
ATC
GEM_GENERAL_TERMS_AND_CONDITIONS
N/a
BHANDARA, MAHARASHTRA
N/a
CHANDRAPUR, MAHARASHTRA
Amravati District Panchayats
AMRAVATI, MAHARASHTRA
Indian Army
N/a
AHMEDNAGAR, MAHARASHTRA
Tender Results
Loading results...
| Category | Specification | Requirement |
|---|---|---|
| GENERIC | A Grid Tied Photo Voltaic (SPV) power plant consists of | SPV array, Module Mounting Structure, Power Conditioning Unit (PCU) consisting of Maximum Power Point Tracker (MPPT), Inverter, and Controls and Protections, interconnect cables and switches |
| GENERIC | PV Array Mounting | Mounted on a suitable structure |
| GENERIC | Grid tied SPV system is | Without battery and designed with necessary features to supplement the grid power during day time. |
| GENERIC | Installation and testing for complete system | Yes including Civil Work, Designing, Fabrication, Cabling Work with suitable Bolts, Nuts, Clamps, Connectors and testing etc., |
| INVERTER | Rated out put power of inverter (Kw) | 2, 4, 1.5, 1, 3, 6, 5, 8 |
| INVERTER | Switching device | IGBT, MOSFET |
| INVERTER | No. of Phase (in Nos.) | 1 |
| INVERTER | Inverter output wave form | Pure sine wave |
| INVERTER | No.of MPPT per inverter (in Nos.) | 4, 2, 1 |
| INVERTER | No. of string at input side of inverter ( input port +ve and -ve) ( hint: 1 sets contains 1 +ve and 1 -ve port) | 1 set, 2 set, 3 set, 4 set |
| INVERTER | Maximum power point tracker | Integrated in the PCU/inverter to maximize energy drawn from the array |
| INVERTER | Operating Voltage Range of Inverter | 50 V to 500 V, 80 to 500 V, 100 V to 500 V, 160 V to 850 V, 200 V to 800 V, 200 V to 1000 V, 90 V to 520 V |
| INVERTER | Over load support at Input side, DC | 15% of Maximum Input Voltage |
| INVERTER | Maximum input current for each MPPT (in A) | 18, 11, 28.5, 22 |
| INVERTER | Service condition | Indoor, Outdoor |
| INVERTER | Ingress protection rating of inverter | IP 65 (for outdoor use), IP 23 (for indoor use), IP 20 (for indoor use) |
| INVERTER | Cooling medium for inverter | Nature air cooled, Constant speed Fan Cooled, Intelligent fan cooling |
| INVERTER | Manual switch for disconnecting DC supply | Yes, No |
| INVERTER | Inverter mounting type | Wall Mounted, Floor Mounted |
| INVERTER OUT PUT | Maximum current for single phase inverter (in A) | 10.5, 15.7, 21, 25, 5.2, 8.1 |
| INVERTER OUT PUT | Output voltage (in V) | 240 V |
| INVERTER OUT PUT | Invert auto trip at output side | Lower : at 160 V, Higher : at 285 V with adjustable |
| INVERTER OUT PUT | Overall Efficiency (in %) | >90, >93, >96, >98 |
| PROTECTION FOR INVERTER | Overlod protection | 110% for 1 Minute,, 125% for 30 sec.,, 150% for 5 sec. |
| PROTECTION FOR INVERTER | Over temperature protection | Yes at 65 Deg. C Cooling Fan will auto switch ON, Yes at 65 Deg. C shutdown |
| PROTECTION FOR INVERTER | Surge protection | Metal Oxide Varistor (MOV) |
| PROTECTION FOR INVERTER | Insulation Resistance Monitoring | Yes, No |
| PROTECTION FOR INVERTER | Grid Monitoring protection | Yes, No |
| PROTECTION FOR INVERTER | Power factor at rated out put power | 0.8, 0.9 |
| PROTECTION FOR INVERTER | Inverter body material | Aluminium Casting, M.S. Plate |
| SERVICE CONDITION | Operating temperature | -25 to +60 deg. C, -20 to +50 deg. C |
| DISPLAY FEATURES ON INVERTER | Type of display | LCD, LED |
| DISPLAY FEATURES ON INVERTER | Display parameters | DC Voltage, DC Current, AC Voltage, AC Current, Out put frequency, Power Factor |
| DISPLAY FEATURES ON INVERTER | Generating power Data storage facility | Yes for 2 Years from the date of commissioning |
| DISPLAY FEATURES ON INVERTER | Interface facility for transmitting the generating power data for cloud storage | Inbuilt Wifi Enabled, With Wifi Dongle, With GPRS Dongle without SIM card, With RS485 |
| DISPLAY FEATURES ON INVERTER | Net meter | Approved by Government of India/State Government authority concerned for connecting to Grid |
| Add on items - DC DISTRIBUTION BOARD | DC Distribution panel to receive the DC output from the array field | Yes with surge arrestors |
| Add on items - DC DISTRIBUTION BOARD | Ingress protection (Enclosure protection) of DC Distribution Box | IP65 |
| Add on items - DC DISTRIBUTION BOARD | Material of bus bar and size | Copper, size as per inverter rating |
| Add on items - DC DISTRIBUTION BOARD | Circuit Breaker for input side (DC side) for each inverter | MCB 10 A, MCB 15 A |
| Add on items - CABLE FOR INPUT | ISI Marked Connecting cables according to Inverter rating for each system | PV Module to Inverter DC |
| Add on items - CABLE FOR INPUT | Electric Cable for Input | 1C x 6 Sq. mm, Copper Cable (as per IS:694:2010 latest) |
| Add on items - CABLE FOR INPUT | Cable Length for PV Module to Inverter, DC (in m) | 5, 10, 15, 20, 25 |
| Add on items - AC DISTRIBUTION BOARD | AC Distribution Panel Board (DPB) for controlling the AC power from PCU/inverter | 1 Phase 230 Volt +/- 10%, 50 HZ +/-3% |
| Add on items - AC DISTRIBUTION BOARD | Panel construction | Metal clad, totally enclosed, floor mounted, air insulated, cubical type with change over switch |
| Add on items - AC DISTRIBUTION BOARD | Ingress protection (Enclosure protection) of AC Distribution Box | IP54 for Indoor, IP65 for outdoor |
| Add on items - AC DISTRIBUTION BOARD | All switches and the circuit breakers, connectors should conform to | IS:60947 part I, II and III |
| Add on items - AC DISTRIBUTION BOARD | Panels designed for minimum expected ambient temperature | 45 deg. C |
| Add on items - AC DISTRIBUTION BOARD | Circuit Breaker for output side (AC side) for each inverter | MCB 10 A, MCB 16 A, MCB 20 A, MCB 25 A, MCB 32 A, MCB 40 A, MCB 63 A, MCB 100 A |
| Add on items - CABLE FOR OUTPUT | ISI Marked Connecting cables according to Inverter rating for each system. | From Inverter to Net Meter, From Inverter to Net Meter and to mains at LT Bus bar while in grid tied mode |
| Add on items - CABLE FOR OUTPUT | Conformity of the specification for cable | 2C x 6 Sq. mm, Copper Cable (as per IS:694:2010 latest), 2C x 10 Sq. mm, Copper Cable (as per IS:694:2010 latest), 2C x 16 Sq. mm, Copper Cable (as per IS:694:2010 latest) |
| Add on items - CABLE FOR OUTPUT | Cable length for output side (from inverter to Net Meter for each system ) (in m ) | 15, 20, 10, 30, 25, 35, 40, 5 |
| Other Add on Items | Cabling work at input side for each system | With PVC Conduit pipe with necessary clamps and screws |
| Other Add on Items | Cabling work at Output side for each system | With Cable Tray with fitment accessories |
| Other Add on Items | Danger boards and signages | 1 No., 2 No., 3 No. |
| ARRAY STRUCTURE | Material of mounting structure | Structural Steel, Grade: E300 (as per IS:2062:2011 latest), Structural Steel, Grade: E350 (as per IS:2062:2011 latest) |
| JUNCTION BOX | Material of Junction Box | GRP( Glass reinforced plastic), FRP (Fibre reinforced plastics), Powder Coated Aluminium, cast aluminiu m alloy |
| WIND LOAD | The Mounting structure shall be so designed to withstand the speed for the wind zone of the location where a PV system is proposed to be installed | Yes |
| WIND LOAD | Compliance to wind velocity test for the Mounting structure of PV System | as per IS 875:1987 part 3 latest |
| WIND LOAD | Regional wind withstand capacity which the Mounting structure of PV system support is suitable to withstand (in Km/Hour) | 180 |
| WARRANTY & GUARANTEE | Minimum guarantee for maintaing of out put peak watt capacity | > / = 90% at the end of 10 years and >/= 80% at the end of 25 years |
Discover companies most likely to bid on this tender
Experience Criteria
Past Performance
Bidder Turnover
Certificate (Requested in ATC)
Additional Doc 1 (Requested in ATC) *In case any bidder is seeking exemption from Experience / Turnover Criteria
the supporting documents to prove his eligibility for exemption must be uploaded for evaluation by the buyer
Ahmednagar District Panchayats
📍 AHMEDNAGAR, MAHARASHTRA
Directorate Of Purchase And Stores
📍 KHAMMAM, TELANGANA
Indo Tibetan Border Police (itbp)
Office Of Dg (ace)
📍 PUNE, MAHARASHTRA
Indian Council Of Agricultural Research (icar)
📍 LOHIT, ARUNACHAL PRADESH
Sign up now to access all documents
Main Document
CATALOG Specification
ATC
GEM_GENERAL_TERMS_AND_CONDITIONS