XLPE Cable for Working Voltages up to and Including 1.1 KV as per IS 7098 (Part 1)
East Coast Railway
VIZIANAGARAM, ANDHRA PRADESH
Bid Publish Date
24-Jan-2026, 10:03 am
Bid End Date
10-Feb-2026, 12:00 pm
Location
Progress
Quantity
1
Bid Type
Two Packet Bid
West Bengal Transport Corporation Limited invites bids for a 3-Phase distribution transformer category, specified for 11 kV > 200 KVA up to 2500 KVA. The procurement includes installation, testing, commissioning, and operator training within the scope, with statutory clearances where applicable. The tender emphasizes energy efficiency levels, BEE star rating, and multiple standard tests, including stage inspections and sound/noise testing. A minimum warranty is expected on receipt and after installation, with optional fittings and accessories detailed. The contract reserves quantity adjustment up to 25%, and requires a dedicated service center in the consignee state, or establishment within 30 days of award, with a 2-year OEM warranty. This is a comprehensive transformer procurement and support package under West Bengal’s Transport Department guidelines.
3-Phase 11 kV distribution transformers
Rated capacity up to 2500 kVA, standard kVA ratings
IS:1180 Part 1:2014 type tests and annexure for insulation, BDV, moisture
Oil conservator and tank construction with specified thickness
Table 12 painting requirements for internal and external surfaces
BEE energy efficiency level and star rating requirements
No-load current at 112.5% voltage test and short-circuit withstand test
Optional fittings: Buchholz relay, oil temp indicators, cable end boxes
Up to 25% quantity variation with extended delivery clauses
2-year OEM warranty post-acceptance or post-installation
Functional Service Centre in-state or establish within 30 days
Supply, installation, testing, commissioning, and operator training included
Stage inspections, sound level, and specific test reports required
Payment terms to be as per purchaser's standard conditions; ensure alignment with 30/60/90 day cycles post acceptance.
Delivery commencement from the last date of original delivery order; option-driven extensions governed by formula with minimum 30 days.
Penalties for delayed delivery and non-conformance to IS 1180 criteria; LD terms to be as per tender terms.
Proven experience supplying 3-Phase distribution transformers up to 2500 kVA
ISI/BIS or IS 1180 compliant product and test documentation
Functional service center in West Bengal or ready to establish within 30 days
Main Document
CATALOG Specification
GEM_GENERAL_TERMS_AND_CONDITIONS
East Coast Railway
VIZIANAGARAM, ANDHRA PRADESH
East Coast Railway
DANTEWADA, CHHATTISGARH
East Coast Railway
DANTEWADA, CHHATTISGARH
Rail Vikas Nigam Limited
VISAKHAPATNAM, ANDHRA PRADESH
Indian Army
CHENNAI, TAMIL NADU
Tender Results
Loading results...
| Category | Specification | Requirement |
|---|---|---|
| STANDARDS | Energy efficiency level | 1 |
| STANDARDS | BEE Star Rating | 1 |
| STANDARDS | Installation, Testing and Demonstration | No |
| STANDARDS | Minimum warranty on receipt of stores (in Months) | 30 |
| STANDARDS | Minimum warranty from the date of installation (in Months) | 24 |
| RATINGS | Nominal system voltage, HV ( in kV) | 11 |
| RATINGS | Nominal system voltage, LV ( in V) | 415 |
| RATINGS | Standard ratings (in kVA) | 250, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000, 2500 |
| RATINGS | Minimum basic insulation level (in kVP) | 75 |
| RATINGS | No load voltage ratios (in Volts) | 11000/433-250 |
| RATINGS | Highest system voltage for equipment (in kV) | 12 |
| RATINGS | Rated lightning impulse withstand voltage (in kV Peak) (Refer IS:1180 (Part 1):2014 Annex-D) | 75 |
| CONSTRUCTION | Core mateial | CRGO (as per IS:3024 latest) |
| CONSTRUCTION | Conductor (Winding) material | Copper |
| CONSTRUCTION | Type of Mounting | Pole Mounted |
| CONSTRUCTION | Noise level at rated voltage and freqeuncy, Maximum (in dB) | 45 |
| TRANSFORMER TANK | Transformer tank cover construction | Non-sealed, Bolted |
| TRANSFORMER TANK | Tank configuration with | With radiator fins |
| TRANSFORMER TANK | Material of transformer tank | Mild Steel |
| TRANSFORMER TANK | Minimum thickness of top and bottom material of transformer tank (in mm) | 6 |
| TRANSFORMER TANK | Minimum thickness of side material of transformer tank (in mm) | 4 |
| TRANSFORMER TANK | Material of Bolts/Nuts/Wahers exposed to atmosphere | Stainless steel (for upto 12 mm size), Brass (for upto 12 mm size), Electro Galvanized (for above 12 mm size), Hot Dip Galvanized (for above 12 mm size) |
| TRANSFORMER TANK | Gaskets wherever used shall conform to | Type III (as per IS:11149) Type C (as per IS:4253 (Pt.2) |
| TRANSFORMER TANK | Provision of conservator | Yes , for Non sealed type with Plain tank construction |
| Painting | Type of painting on inside of tank (hint: Refer Table 12 of IS:1180 (Pt.1):2014) | Oil resistant paint |
| Painting | Type of painting on External surface of tank (hint: Refer Table 12 of IS:1180 (Pt.1):2014) | Epoxy (Primer), Polyurethane (finish coat) |
| TAP CHANGER | Winding tapped | HV |
| TAP CHANGER | No. of positions (in Nos.) | 7 |
| TAP CHANGER | Voltage variation | +5% to -10% in steps of 2.5% for variation of HV |
| TERMINAL ARRANGEMENT | Transformer fitted with bushings of appropriate voltage and curent ratings on HV side | Yes. 3 Nos. (Conforming to IS:2099) |
| TERMINAL ARRANGEMENT | Transformer fitted with bushings of appropriate voltage and curent ratings on LV side | Yes. 4 Nos. (Conforming to IS:7421) |
| TERMINAL ARRANGEMENT | Suitable provision for adoption of cables of suitable size on LV side | Yes. For PVC/XLPE Cables |
| TERMINAL ARRANGEMENT | Cable End Box on HV side | No |
| TERMINAL ARRANGEMENT | Cable End Box on LV side | Yes |
| MARKING | Material of rating plate | Anodized aluminium |
| MARKING | Marking method on rating plate | Etching |
| MARKING | Rating and terminal marking plates combined into one plate | Yes |
| OPTIONAL FITTINGS | Suitable rating lightning arrestors | HT Side, 1 No. per phase |
| OPTIONAL FITTINGS | Bird guard | No |
| OPTIONAL FITTINGS | Terminal connectors | Yes |
| OPTIONAL FITTINGS | Oil temperature indicator and widning temperature indicator | Yes |
| OPTIONAL FITTINGS | Jacking pads | No |
| OPTIONAL FITTINGS | Buchholz relay | NoMagnetic oil level gauge with low oil level alarm contact |
| OPTIONAL FITTINGS | Magnetic oil level gauge with low oil level alarm contact | Yes for transformer above 1600 |
| OPTIONAL FITTINGS | Non return valve | Yes |
| OPTIONAL FITTINGS | Protection relay for sealed type transformers for internal parameters that is pressure, temperature, oil level and gas detection | No |
| OPTIONAL FITTINGS | Unidirectional flat rollers | Yes |
| OPTIONAL FITTINGS | Drain cum sampling valve | Yes with steel plug (for transformers upto 500 KVA) |
| OPTIONAL FITTINGS | Self protection / disconnection devices | No |
| OPTIONAL FITTINGS | Expulsion fuse as disconnection device | No |
| SERVICE CONDITION | Maximum altitude | <5000 m |
| TEST REPORTS & CERTIFICATIONS | Availability of type test reports to prove the confirmity of the specification from | NABL Accrediated |
| TEST REPORTS & CERTIFICATIONS | Agreed for stage Inspection as required by buyer | Yes |
| SPECIAL TEST REPORTS | Availability of test report for Determination of sound level test | No |
| SPECIAL TEST REPORTS | Availability of test report for short circuit withstand test | Yes |
| SPECIAL TEST REPORTS | Availability of test report for No load current at 112.5 % Voltage | Yes |
| SPECIAL TEST REPORTS | Availability of test report for Paint adhesion test | No |
| SPECIAL TEST REPORTS | BDV and moisture content of oil in the transformer | Yes for 1 No. |
| SPECIAL TEST REPORTS | Other requirements | Losses and Impedance values as per Cl.7.8 and Table 6 of IS:1180 (Part 1):2014 latest, Limits of temeprature-rise as per Cl.7.10 of IS:1180 (Part 1):2014 latest |
Discover companies most likely to bid on this tender
GST registration certificate
PAN card
Experience certificates for similar transformer supply/installations
Financial statements or turnover evidence
EMD submission proof (as per tender terms)
Technical bid documents demonstrating IS 1180 compliance
OEM authorization certificates (where applicable)
Warranty certificates from OEM
Key insights about WEST BENGAL tender market
Bidders must submit GST, PAN, and experience certificates along with technical and financial bids. Ensure IS 1180 conformity, 2-year OEM warranty, and evidence of a service center in West Bengal or plans to establish within 30 days. EMD amount should follow tender guidelines and be paid as defined in the terms.
Required documents include GST registration, PAN, experience certificates for similar supply, financial statements, EMD proof, OEM authorizations if applicable, IS 1180 test reports, and warranty certificates from the OEM. Technical bid must demonstrate compliance with energy efficiency and BEE star rating.
Mandatory standards include IS 1180 Part 1:2014 (Annex-D) for impulse withstand and paint adhesion, stage inspections, type test reports, sound level, BDV/oil moisture, and no-load current at 112.5% voltage. Transformers must meet energy efficiency and BEE star rating criteria.
Warranty duration is 2 years from final acceptance or after installation/commissioning. OEM warranty certificates must be submitted at delivery; service support and maintenance teams should be available across India for after-sales service.
The purchaser can increase or decrease quantity up to 25% at contract placement or during currency. Delivery period adjusts based on a formula; minimum extension is 30 days. Successful bidders must adhere to this option clause.
Bidder must have a functional service centre in the state of each consignee location or establish one within 30 days of award. Payment is released after documentary evidence of a functional service centre is provided.
Scope includes supply, installation, testing, commissioning, and training of operators. Statutory clearances, if any, must be provided; training ensures operators can run and maintain the transformer efficiently post-commissioning.
Transformers rated up to 2500 kVA with 11 kV nominal HV and corresponding LV voltage in volts; insulation level, no-load current test, and highest system voltage are clearly defined per IS 1180 standards; bushings and end boxes must suit voltage and current ratings.
Jodhpur VVNL - MD
📍 JODHPUR, RAJASTHAN
Nlc India Limited
📍 CUDDALORE, TAMIL NADU
North Western Railway
📍 SIROHI, RAJASTHAN
North Western Railway
📍 JAIPUR, RAJASTHAN
Nhpc Limited
📍 KULLU, HIMACHAL PRADESH
Sign up now to access all documents
Main Document
CATALOG Specification
GEM_GENERAL_TERMS_AND_CONDITIONS