TANGEDCO (Tamil Nadu Generation and Distribution Corporation Limited) seeks supply of 3-Phase Distribution Transformers covering a rated range from 200 kVA up to 2500 kVA at nominal system voltage 11 kV (HV) and corresponding LV levels, for deployment under Tamil Nadu electricity distribution projects. The procurement includes transformer construction per IS 1180 guidelines, with emphasis on energy efficiency levels, BEE star rating, and installation, testing, and demonstration requirements. EMD: ₹10,000. The awardable quantity is subject to a 25% opt‑in/variation, and delivery timing will align to order issuance and extended periods per option clauses. This tender targets suppliers capable of meeting rigorous safety, performance, and environmental standards across Tamil Nadu.
Distribution transformer category: 3 phase, 11 kV to LV
Rated capacity: 200 kVA to 2500 kVA (inclusive)
Standards: IS 1180 (Part 1): 2014; BEE star rating; energy efficiency level
Paint specification: internal and external coatings per Table 12 IS:1180 Pt.1:2014
Voltage withstand: highest system voltage, no-load current at 112.5% voltage
Tank construction: material, thickness min top/bottom and side; gaskets; conservator provision
Optional fittings: Buchholz relay, oil temp indicators, Bird guard, lightning arrests, protection relays
Testing: type test reports required; sound level, short-circuit withstand, BDV/oil moisture tests
Option clause allows ±25% quantity variation during contract and currency
Delivery period aligns to last date of original order; extension rules given
EMD of ₹10,000; stage inspections and type tests required
Payment terms to be as per buyer ATC; EMD ₹10,000, with possible advance or milestone payments per contract
Delivery must commence from order date; option quantity adjustments allowed up to ±25% with minimum 30 days extension if applicable
Penalties to be defined per ATC; LDs for late delivery and non-conformance to standards
Experience in supplying high voltage distribution transformers (200 kVA to 2500 kVA)
Demonstrated capability to meet IS 1180 and BEE star rating requirements
Availability of type test reports and stage inspection readiness
Indian Army
BARMER, RAJASTHAN
North Eastern Railway
BAREILLY, UTTAR PRADESH
North Eastern Railway
VARANASI, UTTAR PRADESH
Indian Army
WEST DELHI, DELHI
N/a
BALRAMPUR, UTTAR PRADESH
Tender Results
Loading results...
| Category | Specification | Requirement |
|---|---|---|
| STANDARDS | Energy efficiency level | 1 |
| STANDARDS | BEE Star Rating | 1 |
| STANDARDS | Installation, Testing and Demonstration | Yes . Including Civil work |
| STANDARDS | Minimum warranty on receipt of stores (in Months) | 66 |
| STANDARDS | Minimum warranty from the date of installation (in Months) | 60 |
| RATINGS | Nominal system voltage, HV ( in kV) | 11 |
| RATINGS | Nominal system voltage, LV ( in V) | 415 |
| RATINGS | Standard ratings (in kVA) | 250 |
| RATINGS | Minimum basic insulation level (in kVP) | 75 |
| RATINGS | No load voltage ratios (in Volts) | 11000/433-250 |
| RATINGS | Highest system voltage for equipment (in kV) | 12 |
| RATINGS | Rated lightning impulse withstand voltage (in kV Peak) (Refer IS:1180 (Part 1):2014 Annex-D) | 75 |
| CONSTRUCTION | Core mateial | CRGO (as per IS:3024 latest) |
| CONSTRUCTION | Conductor (Winding) material | Copper |
| CONSTRUCTION | Type of Mounting | Ground Mounted |
| CONSTRUCTION | Noise level at rated voltage and freqeuncy, Maximum (in dB) | 48 |
| TRANSFORMER TANK | Transformer tank cover construction | Sealed |
| TRANSFORMER TANK | Tank configuration with | Cooliong tubes |
| TRANSFORMER TANK | Material of transformer tank | Stainless steel |
| TRANSFORMER TANK | Minimum thickness of top and bottom material of transformer tank (in mm) | 7 |
| TRANSFORMER TANK | Minimum thickness of side material of transformer tank (in mm) | 5 |
| TRANSFORMER TANK | Material of Bolts/Nuts/Wahers exposed to atmosphere | Stainless steel (for upto 12 mm size) |
| TRANSFORMER TANK | Gaskets wherever used shall conform to | Type III (as per IS:11149) Type C (as per IS:4253 (Pt.2) |
| TRANSFORMER TANK | Provision of conservator | No |
| Painting | Type of painting on inside of tank (hint: Refer Table 12 of IS:1180 (Pt.1):2014) | Oil resistant paint |
| Painting | Type of painting on External surface of tank (hint: Refer Table 12 of IS:1180 (Pt.1):2014) | Epoxy (Primer) |
| TAP CHANGER | Winding tapped | HV |
| TAP CHANGER | No. of positions (in Nos.) | 7 |
| TAP CHANGER | Voltage variation | +5% to -10% in steps of 2.5% for variation of HV |
| TERMINAL ARRANGEMENT | Transformer fitted with bushings of appropriate voltage and curent ratings on HV side | Yes. 3 Nos. (Conforming to IS:2099) |
| TERMINAL ARRANGEMENT | Transformer fitted with bushings of appropriate voltage and curent ratings on LV side | Yes. 4 Nos. (Conforming to IS:7421) |
| TERMINAL ARRANGEMENT | Suitable provision for adoption of cables of suitable size on LV side | Yes. For PVC/XLPE Cables |
| TERMINAL ARRANGEMENT | Cable End Box on HV side | Yes |
| TERMINAL ARRANGEMENT | Cable End Box on LV side | Yes |
| MARKING | Material of rating plate | Stainless steel |
| MARKING | Marking method on rating plate | Stamped |
| MARKING | Rating and terminal marking plates combined into one plate | Yes |
| OPTIONAL FITTINGS | Suitable rating lightning arrestors | HT Side, 1 No. per phase |
| OPTIONAL FITTINGS | Bird guard | Yes |
| OPTIONAL FITTINGS | Terminal connectors | Yes |
| OPTIONAL FITTINGS | Oil temperature indicator and widning temperature indicator | Yes |
| OPTIONAL FITTINGS | Jacking pads | No |
| OPTIONAL FITTINGS | Buchholz relay | NoMagnetic oil level gauge with low oil level alarm contact |
| OPTIONAL FITTINGS | Magnetic oil level gauge with low oil level alarm contact | Yes for transformer above 1600 |
| OPTIONAL FITTINGS | Non return valve | Yes |
| OPTIONAL FITTINGS | Protection relay for sealed type transformers for internal parameters that is pressure, temperature, oil level and gas detection | Yes |
| OPTIONAL FITTINGS | Unidirectional flat rollers | Yes |
| OPTIONAL FITTINGS | Drain cum sampling valve | Yes with steel plug (for transformers upto 500 KVA) |
| OPTIONAL FITTINGS | Self protection / disconnection devices | On secondary side (as per IS/IEC:60947-2:2003 |
| OPTIONAL FITTINGS | Expulsion fuse as disconnection device | No |
| SERVICE CONDITION | Maximum altitude | <1000 m |
| TEST REPORTS & CERTIFICATIONS | Availability of type test reports to prove the confirmity of the specification from | NABL Accrediated |
| TEST REPORTS & CERTIFICATIONS | Agreed for stage Inspection as required by buyer | Yes |
| SPECIAL TEST REPORTS | Availability of test report for Determination of sound level test | Yes |
| SPECIAL TEST REPORTS | Availability of test report for short circuit withstand test | Yes |
| SPECIAL TEST REPORTS | Availability of test report for No load current at 112.5 % Voltage | Yes |
| SPECIAL TEST REPORTS | Availability of test report for Paint adhesion test | Yes for 1 No. |
| SPECIAL TEST REPORTS | BDV and moisture content of oil in the transformer | Yes for 1 No. |
| SPECIAL TEST REPORTS | Other requirements | Losses and Impedance values as per Cl.7.8 and Table 6 of IS:1180 (Part 1):2014 latest |
Discover companies most likely to bid on this tender
GST registration certificate
Permanent Account Number (PAN) card
Experience certificates for similar transformer supply
Financial statements (audited if available)
EMD submission proof
Technical bid document demonstrating IS 1180 compliance
OEM authorization letters (if applicable)
Type test reports and any stage inspection approvals
Key insights about TAMIL NADU tender market
To bid, prepare GST and PAN, provide experience certificates for HV transformer supply, attach EMD ₹10,000, and include type test reports; ensure IS 1180 compliance, BEE star rating, and stage inspection readiness; submit OEM authorizations if applicable and financial statements.
Required documents include GST certificate, PAN, experience certificates for HV transformer supply, financial statements, EMD proof of ₹10,000, OEM authorization letters, and IS 1180-compliant technical bid with stage/test reports and painting specifications per Table 12.
Key standards include IS 1180 (Part 1): 2014, mandatory stage inspections, BDV and moisture tests, paint adhesion tests, and energy efficiency levels with BEE star rating to be demonstrated by the supplier.
EMD is ₹10,000; bidders must submit proof of payment or online transfer as part of bid security, with reference in the bid submission and eligibility validation.
The buyer reserves an option to increase or decrease quantity by up to 25% during contract; extended delivery periods follow the formula (additional quantity/original quantity) × original delivery period with a minimum of 30 days.
Mandatory testing reports include type test certificates, short-circuit withstand test, sound level test, BDV/oil moisture tests, paint adhesion, and confirmation of conformity to IS 1180 specifications; stage inspection may be required by buyer.