TenderDekho Logo
GEM

Invitation to Bid - Diesel Power Generator (up to 900 KVA) in KAMRUP, ASSAM

Bid Publish Date

17-Jul-2026, 3:19 pm

Bid End Date

07-Aug-2026, 4:00 pm

Location

KAMRUP , ASSAM

Progress

Issue17-Jul-2026, 3:19 pm
AwardPending
Explore all 6 tabs to view complete tender details

Quantity

1

Bid Type

Two Packet Bid

Categories 5

N/a has released a public tender for Diesel Power Generator (up to 900 KVA) (Q2) in KAMRUP, ASSAM. Quantity: 1. Submission Deadline: 07-08-2026 16: 00: 00. Download documents and apply online.

Additional Tender Data

Commercial Details

Tender Category

Goods

Bid To RA

No

Bid To RA Enabled

Yes

Item Category

Diesel Power Generator (up to 900 KVA) (Q2)

Advisory Bank

State Bank of India

ePBG Percentage

5%

ePBG Duration (Months)

40

Delivery Details

Max Delivery Days

60

Delivery Locations

1

Delivery Cities

Kamrup Metro

Delivery Pincodes

782402

Delivery Locations

ConsigneeAddressCityStatePincodeQuantityDelivery DaysAdditional Requirement
Hemanta Sarma782402,Nazirakhat, SonapurKamrup MetroAssam782402160-

BID & GeM Expert Consultancy

End-to-end support — bid preparation, GeM registration, document filing & compliance by industry experts.

Bid Preparation GeM Registration Document Filing

Free consultation · 24h response

Documents 4

GeM-Bidding-9354589.pdf

Main Document

CATALOG-Specification-1

CATALOG Specification

Other Documents

OTHER

GEM General Terms and Conditions Document

GEM_GENERAL_TERMS_AND_CONDITIONS

Past Similar Tenders (Historical Results)

5 found

Central Board of Direct Taxes Diesel Generator Tender 900 KVA Ghaziapur Uttar Pradesh 2026

Central Board Of Direct Taxes (cbdt)

BALLIA, UTTAR PRADESH

Posted: 14 March 2026
Closed: 18 March 2026
GEM

CBDT Diesel Power Generator Tender up to 900 KVA Fatehpur Uttar Pradesh 2026 ISO 9001 IS 550

Central Board Of Direct Taxes (cbdt)

FATEHPUR, UTTAR PRADESH

Posted: 14 March 2026
Closed: 18 March 2026
GEM

Kerala Local Self Government Department Diesel Generator Tender Pathanamthitta 900 KVA CPWD Gen Spec 2026

N/a

PATHANAMTHITTA, KERALA

Posted: 16 March 2026
Closed: 28 March 2026
GEM

Diesel Power Generator (up to 900 KVA)

N/a

UDHAM SINGH NAGAR, UTTARAKHAND

Posted: 16 March 2026
Closed: 15 April 2026
GEM

Diesel Power Generator (up to 900 KVA)

E-municipalities - Eservices To Citizens And Employees Of Urban Local Bodies Of Uttar Pradesh

GORAKHPUR, UTTAR PRADESH

Posted: 17 March 2026
Closed: 27 March 2026
GEM

Technical Specifications 1 Item

Item #1 Details

View Catalog
Category Specification Requirement
Installation Configuration Power Generator Installation Configurations as per CPWD General Specifications for Electrical Works – Part VII (DG Set) Fixed (Power Generators are permanently installed)"
Ratings Nominal Rated Capacity (in kVA) 125
Ratings Number of Phase Three Phase
Engine Rated Engine Power (kWm) 110 % of the required powered at STP(Standard Temperature Pressure) i.e equal to (Nominal Rated Capacity (KVA) of power generator Any Auxilary power Consumption by the Power generator) x Power factor(0.8) / Alternator efficience Or higher
Engine Type of Engine Cooling Liquid Cooled
Engine Type of Governor Electronic Or higher
Engine Number of Cylinders 4, 6
Engine Rated Engine Speed (in RPM) 1500
Engine Type of Fuel High Speed Diesel (HSD)
Alternator Alternator Voltage Rating 415.0
Alternator Conformity to Indian Standard For Alternator Generally conforming to IS:13364 (Part-2) latest (Above 20 KVA)
Alternator Voltage Regulation Grade VG 3 Or higher
Alternator Alternator IP (Ingress Protection) Rating IP 23 Or higher
Control Panel Type of Control Panel Manual Control Panel
Control Panel Control Panel Location Inside the canopy
Control Panel Display Meters in Control Panel (with Appropriate Rating and Accuracy Class) - Included in Scope of Supply Multifunctional Digital display meter (displaying Voltage, Current, Frequency, Power Factor)
Fuel Tank Fuel Tank Capacity 200.0, 230.0, 240.0, 250.0, 292.0, 300.0
Fuel Tank Number of Fuel Tank 1
Battery Battery Type "Low Maintenance free to IS: 14257 for high cranking performance"
Salient Features Salient Features of Power Generator Glass window on Accoustic Enclosure in front of the Control Panel, Emergency Stop outside the Accoustic Enclosure
Trailer Availability of Trailer NA for Fixed/Skid Mounted Power Generator
Installation Requirement Scope of installation for diesel generating set when offered by the vendor - inclusive in the scope of supply (Part-1) a) Installation of Power Generator when offered by the vendor is inclusive in the scope of supply and shall be done by the seller. The installation work of Power Generator and its constituent parts shall be generally conforming to CPWD General Specification for Electrical Works, Part - VII - latest. b) Foundation shall be constructed by the seller. Foundation shall be of PCC type with the ratio of 4:2:1. The length and breadth of the foundation shall be 300 mm more from the respective length and breadth of the Power Generator. The height of the foundation shall be 400 mm, i.e., 200 mm below and 200 mm above the ground level. All the materials / labour required for foundation work shall be supplied by the seller.
Installation Requirement Scope of installation for diesel generating set when offered by the vendor - inclusive in the scope of supply (Part-2) c) Supply, laying and termination of interconnecting power and control cable shall be done by the seller. The cable supplied shall be ISI marked heavy duty PVC insulated, armoured cable, with PVC outer Sheath of Type ST-2 (FR Grade, Category C1), with aluminium conductor having insulation of PVC compound type -C, suitable for rated voltage upto and including 1100 volts and conforming to IS: 1554 (Part-1) latest. For 3-Phase Power Generators, 3.5 core or higher core cables shall be used. Total length of the cable supplied by the seller shall be within 30 meters for each Power Generator with manual control panel and within 60 metres for each Power Generator with AMF control panel. The current rating of the cables shall be as indicated below: 2C, 6 Sq mm for Single Phase, 3.5 & 5.0 KVA 2C, 10 Sq mm for Single Phase, 7.5 & 10 KVA 2C, 25 Sq mm for Single Phase, 15 KVA 2C, 35 Sq mm for Single Phase, 20 KVA 2C, 70Sq mm for Single Phase, 25 KVA 2C, 95Sq mm for Single Phase, 30 KVA 2C, 120Sq mm for Single Phase, 40 KVA 4C, 4 Sq mm for Three Phase,
Installation Requirement Scope of installation for diesel generating set when offered by the vendor - inclusive in the scope of supply (Part-4) e) Construction of suitable earthing station and necessary connections shall be done by the seller. All the materials / labour required for construction of earthing station shall be supplied by the seller. The total number of earthing pits/stations shall be 4, i.e., 2 for neutral and 2 for body-earthing. Netutral earthing shall be done with copper Plate and Body earthing shall be done with G.I. plate / Copper. The consignee should choose installation site in such a way that the earthing stations can be made within 10 metres of the Power Generator. Earthing station shall be typically constructed as per prevalent standard practices and shall be generally conforming to CPWD General specification for Electrical Works, Part - VII & Part - I - latest. e) Installation of Fuel Tank including foundation / stand shall be done by the seller. f)The warranty is applicable upto specified value of month/hours whichever occurs first's.
Installation Requirement Above Scope of Installation for the Diesel Generating Set, when offered by the vendor, has been seen, read, understood, and agreed to Comply Yes
Warranty/Services Number of Preventive Maintenance Visits Offered in an Year During Warranty Period (Supply of all consumables is the buyer's responsibilty) 2
Test Reports Type of lab which carried out test of complete product to prove the conformity of product specification Certificates required as per CPCB

🤖 AI-Powered Bidder Prediction

Discover companies most likely to bid on this tender

Live AI
Historical Data

Required Documents

1

Experience Criteria

2

Certificate (Requested in ATC)

3

OEM Authorization Certificate

4

Additional Doc 1 (Requested in ATC)

5

Additional Doc 2 (Requested in ATC)

6

Compliance of BoQ specification and supporting document *In case any bidder is seeking exemption from Experience / Turnover Criteria

7

the supporting documents to prove his eligibility for exemption must be uploaded for evaluation by the buyer

Similar Tenders

5 found

Diesel Power Generator (up to 900 KVA)

Southern Railway

📍 CHENNAI, TAMIL NADU

EMD: ₹2.4 L
⏰ Deadline: 2 weeks left
🛒 Type: Goods
View GEM

Diesel Power Generator (up to 900 KVA)

Director General Of National Cadet Corps (dgncc)

📍 GORAKHPUR, UTTAR PRADESH

⏰ Deadline: 2 weeks left
🛒 Type: Goods
View GEM
Urgent

Diesel Power Generator (up to 900 KVA)

State Urban Development Authority

📍 DEHRADUN, UTTARAKHAND

EMD: ₹1.8 L
⏰ Deadline: 3 days left
🛒 Type: Goods
View GEM
Urgent

Diesel Power Generator (up to 900 KVA)

Inspector General Of Registration

📍 BASTI, UTTAR PRADESH

EMD: ₹29,050
Est: ₹29.1 L
⏰ Deadline: 3 days left
🛒 Type: Goods
View GEM
Urgent

Indian Army Diesel Power Generator Tender 900 KVA CPWD DG Set Standards 2026

Indian Army

📍 THIRUVANANTHAPURAM, KERALA

⏰ Deadline: 3 days left
🛒 Type: Goods
View GEM