Indian Army RAM 8GB DDR4, DVD Writer Slim, Keyboard with Mouse, UPS 1KVA Tender 2026 – Department of Military Affairs
Indian Army
JALANDHAR, PUNJAB
Bid Publish Date
07-Feb-2026, 4:55 pm
Bid End Date
27-Feb-2026, 8:00 pm
EMD
₹27,000
Value
₹13,23,204
Progress
Quantity
1
Bid Type
Two Packet Bid
Directorate General Of Lighthouses And Lightships announces a tender for Power Generator - DG Set (up to 900 KVA) (Q2). Quantity: 1. Submission Deadline: 27-02-2026 20: 00: 00. Last date to apply is approaching fast!
Main Document
CATALOG Specification
OTHER
ATC
GEM_GENERAL_TERMS_AND_CONDITIONS
Indian Army
JALANDHAR, PUNJAB
Indian Army
BARAMULLA, JAMMU & KASHMIR
Indian Army
AMRITSAR, PUNJAB
Indian Army
BUDGAM, JAMMU & KASHMIR
Indian Army
BUDGAM, JAMMU & KASHMIR
Tender Results
Loading results...
| Category | Specification | Requirement |
|---|---|---|
| Power Generator INSTALLATION CONFIGURATIONS | Power Generator installation configurations as defined in CPWD General Specifications for Electrical works - Part VII (DG Set) | Fixed (Power Generators are permanently installed)", Transportable (Skid Mounted) (Power Generators are not permanently installed)", Mobile (Trailer mounted) (Power Generators having an integral chassis fitted with wheels) " |
| OUTPUT CAPACITY RATING/ PHASE | Nominal Rated Capacity (kVA) | 25 |
| ENGINE | Rated Engine Power (kWm) | 100 % of the required powered at STP(Standard Temperature Pressure) i.e equal to (Nominal Rated Capacity (KVA) of power generator + Any Auxilary power Consumption by the Power generator) x Power factor(0.8) / Alternator efficience, 110 % of the required powered at STP(Standard Temperature Pressure) i.e equal to (Nominal Rated Capacity (KVA) of power generator Any Auxilary power Consumption by the Power generator) x Power factor(0.8) / Alternator efficience Or higher |
| ENGINE | Type of Engine cooling | Liquid Cooled |
| ENGINE | Type of governer | Electronic Or higher |
| ENGINE | Number of cylinders (nos) | 3 |
| ENGINE | Rated RPM of Engine (RPM) | 1500 |
| ENGINE | Fuel | High Speed Diesel (HSD) |
| ENGINE | Starting voltage (volt) | 12 |
| ENGINE | Salient Features of Engine | Turbo Charged Engine, Naturally aspirated engine, Direct injection Fuel System, CRDi Fuel System, cold start upto (-20 deg c ), Indirect injection (IDI) Fuel System, Ambient working temperature upto 55 degree celcius. |
| ALTERNATOR | Alternator Voltage Rating | 415.0, 230.0 |
| ALTERNATOR | Efficiency at rated Power factor at 75% of full Load | 87.0 - 100.0 Or higher |
| ALTERNATOR | Voltage Regulation Grade | VG 1, VG 2, VG 3 Or higher |
| ALTERNATOR | Alternator IP Rating | IP 23 Or higher |
| CONTROL PANEL | Control Panel | Manual Control Panel, AMF Control Panel |
| CONTROL PANEL | Control Panel Location | Inside the canopy, Outside the Canopy |
| CONTROL PANEL | IP Rating of Control Panel | IP 53, IP 54, IP 55 Or higher |
| CONTROL PANEL | Other devices in the control panel (with appropriate rating) - inclusive in the scope of supply | Required switches and cutout, MCB, MCCB, Contactor, Circuit breaker, Battery charger, remote monitoring over internet with GSM modem. |
| CONTROL PANEL | Displayed parameters/Features | Engine Speed, Lube oil pressure, Coolant/cylinder head Temperature, Engine running hours, Engine battery voltage, Engine Running status, Generator Voltage (Ph-Ph), Generator Voltage (Ph-N), Generator Current (R, Y, B), Generator apparent Power (kVA), Generator active Power (kW), Powerfactor, Frequency, Fuel level, Event log, Control supply Voltage, Temperature scanner (RTD,BTD) |
| CONTROL PANEL | Indicators | Low Lube oil pressure, High water / coolant / cylinder head temperature, Low fuel level, Over speed |
| TRAILER | Trailer | Yes, NA for Fixed/Skid Mounted Power Generator |
| TRAILER | Pay load of the Trailer | 0, 500, 1000, 2000 Or higher |
| SCOPE OF INSTALLATION | Installation | Without installation, with installation - inclusive in the scope of supply Or higher |
| WARRANTY/SERVICES | Warranty on Complete power genertor/DG Set | 12, 24, 36 Or higher |
| WARRANTY/SERVICES | Number of preventive maintenance visits offered in an year during warranty period (Supply of all consumables is the buyer's responsibilty)* | 1, 2, 3 |
| TEST REPORTS | Test report Available for (Test/approval) | Type Approval Certificate for the specified rating of the Power Generator from any of the designated agency authorized by CPCB, COP Certificate for engine, Type test report and Endurance test report for Engine as per IS: 10001 latest / IS: 10002 latest, Type test report for Alternator as per IS:13364 (Part-1) latest / IS:13364 (Part-2) latest to prove conformity to the specifications |
Discover companies most likely to bid on this tender
Experience Criteria
Past Performance
Bidder Turnover
Certificate (Requested in ATC)
OEM Authorization Certificate
OEM Annual Turnover
Additional Doc 1 (Requested in ATC)
Compliance of BoQ specification and supporting document *In case any bidder is seeking exemption from Experience / Turnover Criteria
the supporting documents to prove his eligibility for exemption must be uploaded for evaluation by the buyer
N/a
📍 BIJAPUR, CHHATTISGARH
N/a
📍 BIJAPUR, CHHATTISGARH
Aligarh Muslim University (amu)
📍 ALIGARH, UTTAR PRADESH
Hindustan Petroleum Corporation Ltd
📍 VADODARA, GUJARAT
Indo Tibetan Border Police (itbp)
📍 LEH, JAMMU & KASHMIR
Sign up now to access all documents
Main Document
CATALOG Specification
OTHER
ATC
GEM_GENERAL_TERMS_AND_CONDITIONS