Repair and Overhauling Service - diesel generators- DG Sets; REPAIR AND REWINDING OF 19 KVA GEN SET
Indian Army
BARMER, RAJASTHAN
Progress
Quantity
1
Bid Type
Two Packet Bid
Public procurement opportunity for North Western Railway Higher Rating Diesel Generating Sets (1010 kVA and above) (Q3) in Ajmer, RAJASTHAN. Quantity: 1 issued by. Submission Deadline: 20-02-2026 12: 00: 00. View full details and respond.
Main Document
CATALOG Specification
GEM_GENERAL_TERMS_AND_CONDITIONS
Indian Army
BARMER, RAJASTHAN
Indian Army
Rangareddi, TELANGANA
Indian Air Force
BAREILLY, UTTAR PRADESH
Indian Air Force
LEH, JAMMU & KASHMIR
Indian Air Force
Tender Results
Loading results...
| Category | Specification | Requirement |
|---|---|---|
| ENGINE | Type of Engine cooling | Radiator Cooled |
| ENGINE | Type of governer | Electronic, Electronic-Isochronous Or higher |
| ENGINE | Class of governer | A1, A0 Or higher |
| ENGINE | Cylinder arrangement | V-Type |
| ENGINE | Starting System | 24 Volt Dc Electrical |
| ENGINE | "Salient Features of Engine | Turbo Charged Engine, CRDi Fuel System |
| OUTPUT CAPACITY RATING/ PHASE | Nominal Rated Capacity (kVA) | 1010 |
| ALTERNATOR | Alternator Voltage Rating | 415.0 |
| ALTERNATOR | Wiring System | 4 Wire |
| ALTERNATOR | Efficiency at rated Power factor at 75% of full Load | 96.2 - 100.0 Or higher |
| ALTERNATOR | Conformity to Indian Standard (for Alternator) | Generally conforming to IS:13364 (Part-2) latest |
| ALTERNATOR | Type of excitation (for Alternator) | Self excitation Or higher |
| ALTERNATOR | Voltage Regulation Grade upto 1250 kVA | VG 3 Or higher |
| ALTERNATOR | Voltage Regulation Grade above 1250 kVA | NA, G 1, G 2, G 3 Or higher |
| ALTERNATOR | Alternator IP Rating | IP 23 Or higher |
| CONTROL PANEL | Control Panel | AMF |
| CONTROL PANEL | Location of Control Panel | Outside the Acoustic Encolsure |
| CONTROL PANEL | IP Rating of Control Panel | IP 55 Or higher |
| CONTROL PANEL | "Display parameters (hint:- Select displayed parameters on panel)" | Engine Speed, Lube oil pressure, Coolant Temperature, Engine running hours, Engine battery voltage, Engine Running status, Generator Voltage (Ph-Ph), Generator Voltage (Ph-N), Generator Current (R, Y, B), Generator apparent Power (kVA), Generator active Power (kW), Powerfactor, Frequency, Fuel level, Event log, Control supply Voltage, Indicaion lamp |
| CONTROL PANEL | "Indicators (hint:- Select applicable indicators only)" | Low Lube oil pressure, High water / coolant temperature, Low fuel level, Over speed |
| ACOUSTIC ENCLOSURE | Acoustic Enclosure inclusive in the scope of supply | With Acoustic Enclosure |
| ACOUSTIC ENCLOSURE | "Sheet Thickness of accoustic enclosure (May Specify '0' in case of without acoustic enclosure)" | 1.6 mm, 1.8 mm, 2.0 mm Or higher |
| ACOUSTIC ENCLOSURE | "Thickness of fire retardent rock wool insulation (May Specify '0' in case of without acoustic enclosure)" | 100.0 |
| ACOUSTIC ENCLOSURE | "Density of insulation (kg/m3) (May Specify '0' in case of without acoustic enclosure)" | 64 |
| ACOUSTIC ENCLOSURE | "Noise level with acoustic Enclosure at 1 meter (can only be demostrated at OEM's works)" | <= 85 dB |
| ACOUSTIC ENCLOSURE | Salient Features of Acoustic Enclosure | Glass door on Accoustic Enclosure in front of the Control Panel, Illumination arrangement inside acoustic enclosure, Emergency Stop outside the Accoustic Enclosure, NA |
| BATTERY | BATTERY | Low Maintenance free to IS: 14257 for high cranking performance |
| BATTERY | Battery capacity (Ah) | 180 |
| FUEL TANK | Number of Fuel Tanks supplied with each DG Set (inclusive in the scope of supply) | 1, 2 Or higher |
| FUEL TANK | Capacity of each Fuel Tank | 990 litres Or higher |
| SCOPE OF INSTALLATION | Installation | With Installation - inclusive in the scope of supply |
| SCOPE OF INSTALLATION | Scope of installation for Diesel Generating Set(Part-1) when offered by the vendor - inclusive in the scope of supply | Scope of installation when offered by the seller (With Installation - inclusive in the scope of supply) :- a) Installation of DG Set when offered by the vendor is inclusive in the scope of supply and shall be done by the seller. The installation work of DG Set and its constituent parts shall be generally conforming to CPWD General specification for Electrical Works, Part - VII - latest. b) Foundation shall be constructed by the seller. Foundation shall be of PCC type with the ratio of 4:2:1. The length and breadth of the foundation shall be 300 mm more from the respective length and breadth of the DG set. The height of the foundation shall be 400 mm, i.e., 200 mm below and 200 mm above the ground level. All the materials / labour required for foundation work shall be supplied by the seller. |
| SCOPE OF INSTALLATION | Scope of installation for Diesel Generating Set (Part 2 )when offered by the vendor - inclusive in the scope of supply | c) Supply, laying and termination of interconnecting power and control cable between Seller's supplied equipments shall be done by the seller. The interconnecting cable supplied along with each DG Set shall be of suitable current rating and shall be sufficient for a distance of 60 metres. For DG Sets having voltage rating upto 415 Volts, the cable supplied shall be ISI marked heavy duty PVC insulated, armoured cable, with PVC outer Sheath of Type ST-2 (FR Grade, Category C1), with aluminium conductor having insulation of PVC compound type -C, suitable for rated voltage upto and including 1100 volts and conforming to IS: 1554 (Part-1) latest. For DG Sets having voltage rating from 3300 Volts upto and including 33000 Volts, the cable supplied shall be ISI marked XLPE, armoured cable, with PVC outer Sheath of Type ST-2 (FR Grade, Category C1), with copper conductor having XLPE insulation, suitable for rated voltage from 3.3 kV upto and including 33 kV and conforming to IS: 7908 (Part-2) latest. |
| SCOPE OF INSTALLATION | Scope of installation for Diesel Generating Set (Part 3 )when offered by the vendor - inclusive in the scope of supply | d) Construction of suitable earthing station and necessary connections shall be done by the seller. All the materials / labour required for construction of earthing station shall be supplied by the seller. The total number of earthing pits/stations shall be 4, i.e., 2 for neutral and 2 for body-earthing. Netutral earthing shall be done with copper Plate and Body earthing shall be done with G.I. plate / Copper. The consignee should choose installation site in such a way that the earthing stations can be made within 10 metres of the DG set. Earthing station shall be typically constructed as per prevalent standard practices and shall be generally conforming to CPWD General specification for Electrical Works, Part - VII & Part - I - latest. e) Installation of Fuel Tank(s) including foundation / stand, where applicable, shall be done by the seller. |
| SCOPE OF INSTALLATION | Above Scope of installation for Diesel Generating Set(Part-1 + Part-2 + Part-3) when offered by the vendor has been seen, read, understood and agreed to comply | Yes |
| WARRANTY & SERVICING | Warranty | 24 Or higher |
| TEST REPORTS | Test report issuing authority for Engine Rating as per IS: 13018 latest / ISO 3046-latest | Engine Manufacturer |
| TEST REPORTS | Availability of Type test report for Alternator from Central government/NABL/ILAC accridited laboratory to prove conformity to the specifications | Yes |
| TEST REPORTS | If Yes, Alternator Type Test Report to be furnished to the Buyer on demand | Yes |
Discover companies most likely to bid on this tender
Experience Criteria
Past Performance
Certificate (Requested in ATC)
OEM Authorization Certificate *In case any bidder is seeking exemption from Experience / Turnover Criteria
the supporting documents to prove his eligibility for exemption must be uploaded for evaluation by the buyer
Indian Navy
📍 VISAKHAPATNAM, ANDHRA PRADESH
Nhpc Limited
📍 CHAMBA, HIMACHAL PRADESH
Indian Air Force
📍 JAMNAGAR, GUJARAT
Indian Air Force
📍 BAREILLY, UTTAR PRADESH
N/a
📍 BALRAMPUR, UTTAR PRADESH
Sign up now to access all documents
Main Document
CATALOG Specification
GEM_GENERAL_TERMS_AND_CONDITIONS